Application Note  
The VI-ARM Autoranging Rectifier Module (ARM) provides  
an effective solution for the AC front end of a power supply  
built with Vicor DC-DC converters. This high performance  
power system building block satisfies a broad spectrum of  
requirements and agency standards.  
If the bus voltage is less than 200V as the slope nears  
zero, the voltage doubler is activated, and the bus voltage  
climbs exponentially to twice the peak line voltage.  
If the bus voltage is greater than 200V, the doubler is  
not activated.  
2.1  
3.1  
If the bus voltage is greater than 235V as the slope  
approaches zero, the inrush limiting thermistor is  
bypassed. Below 235V, the thermistor is not bypassed.  
The ARM contains all of the power switching and control  
circuitry necessary for autoranging rectification, inrush current  
limiting, and overvoltage protection. This module also provides  
converter enable and status functions for orderly power  
up/down control or sequencing. To complete the AC front end  
configuration, the user needs only to add holdup capacitors and  
a suitable input filter with transient protection.  
The converters are enabled 50 milliseconds after the  
thermistor bypass switch is closed.  
4.1  
5.1  
Bus-OK is asserted after an additional 50 millisecond  
delay to allow the converter outputs to settle within  
specification.  
Functional Description  
The switch that bypasses the inrush limiting PTC (positive  
temperature coefficient) thermistor is open when power is  
applied, as is the switch that engages the strap for voltage  
doubling. (See Fig. 6). In addition, the converter modules are  
disabled via the Enable (EN) line, and Bus-OK (B OK) is high.  
Power-Down Sequence. (See Fig. 7). When input power is  
turned off or fails, the following sequence occurs as the bus  
voltage decays:  
Bus-OK is deasserted when the bus voltage falls below  
205Vdc (Typ.).  
1.2  
Power-Up Sequence. (See Fig. 7).:  
Upon application of input power, the output bus capacitors  
begin to charge. The thermistor limits the charge current,  
and the exponential time constant is determined by the  
holdup capacitor value and the thermistor cold resistance.  
The slope (dv/dt) of the capacitor voltage approaches  
zero as the capacitors become charged to the peak of the  
AC line voltage.  
The converters are disabled when the bus voltage falls  
below 200Vdc. If power is reapplied after the converters  
are disabled, the entire power-up sequence is repeated. If  
a momentary power interruption occurs and power is  
reestablished before the bus reaches the disable threshold,  
the power-up sequence is not repeated.  
1.1  
2.2  
Power  
Up  
Power  
Down  
+Out  
90–132V  
AC Line  
PTC  
Thermistor  
Strap  
400  
L
Strap  
–Out  
300  
200  
100  
0
Output  
Bus  
1.1  
(Vdc)  
2.1  
Strap  
N
PTC  
3.1  
Thermistor  
Bypass  
EN  
4.1  
Converter  
Enable  
Bus OK  
2.2  
Microcontroller  
50ms  
BOK  
5.1  
1.2  
50ms  
Figure 6—Functional block diagram  
Figure 7—Timing diagram: power up/down sequence  
Vicor Corp. Tel: 800-735-6200, 978-470-2900 Fax: 978-475-6715  
ARM, Autoranging Rectifier Module  
Rev. 2.4  
Page 5 of 12  