 浏览型号DCM4623TD2K26E0M70的Datasheet PDF文件第14页浏览型号DCM4623TD2K26E0M70的Datasheet PDF文件第15页浏览型号DCM4623TD2K26E0M70的Datasheet PDF文件第16页浏览型号DCM4623TD2K26E0M70的Datasheet PDF文件第17页浏览型号DCM4623TD2K26E0M70的Datasheet PDF文件第19页浏览型号DCM4623TD2K26E0M70的Datasheet PDF文件第20页浏览型号DCM4623TD2K26E0M70的Datasheet PDF文件第21页浏览型号DCM4623TD2K26E0M70的Datasheet PDF文件第22页  
DCM4623xD2K26E0y7z  
immediately stops switching, and the output voltage of the converter  
falls. The converter remains disabled for a time tFAULT. Once recovered  
and provided the converter is still enabled, the powertrain will again  
Input Fuse Selection  
The DCM is not internally fused in order to provide flexibility in  
configuring power systems. Input line fusing is recommended at the  
system level, in order to provide thermal protection in case of  
catastrophic failure. The fuse shall be selected by closely matching  
system requirements with the following characteristics:  
enter the soft start sequence after tINIT and tON  
.
Temperature Fault Protections (OTP)  
The fault logic monitors the internal temperature of the converter. If  
the measured temperature exceeds TINT-OTP, a temperature fault is  
registered. As with the under voltage fault protection, once a  
temperature fault is registered, the powertrain immediately stops  
switching, the output voltage of the converter falls, and the converter  
remains disabled for at least time tFAULT. Then, the converter waits for  
the internal temperature to return to below TINT-OTP before  
n Current rating (usually greater than the DCM converter’s  
maximum current)  
n Maximum voltage rating (usually greater than the maximum  
possible input voltage)  
n Ambient temperature  
recovering. Provided the converter is still enabled, the DCM will  
n Breaking capacity per application requirements  
n Nominal melting I2t  
restart after tINIT and tON  
.
Output Overvoltage Fault Protection (OVP)  
n Recommended fuse: See Agency Approvals for Recommended Fuse  
http://www.vicorpower.com/dc-dc/isolated-  
regulated/dcm#Documentation  
The converter monitors the output voltage during each switching  
cycle by a corresponding voltage reflected to the primary side control  
circuitry. If the primary sensed output voltage exceeds VOUT-OVP, the  
OVP fault protection is triggered. The control logic disables the  
powertrain, and the output voltage of the converter falls.  
Fault Handling  
Input Undervoltage Fault Protection (UVLO)  
This type of fault is latched, and the converter will not start again  
until the latch is cleared. Clearing the fault latch is achieved by either  
disabling the converter via the EN pin, or else by removing the input  
The converter’s input voltage is monitored to detect an input under  
voltage condition. If the converter is not already running, then it will  
ignore enable commands until the input voltage is greater than  
power such that the input voltage falls below VIN-INIT  
.
VIN-UVLO+. If the converter is running and the input voltage falls  
below VIN-UVLO-, the converter recognizes a fault condition, the  
powertrain stops switching, and the output voltage of the unit falls.  
External Output Capacitance  
The DCM converter internal compensation requires a minimum  
external output capacitor. An external capacitor in the range of 220  
to 2200 µF with ESR of 10 mΩ is required, per DCM for control loop  
compensation purposes.  
Input voltage transients which fall below UVLO for less than tUVLO  
may not be detected by the fault proection logic, in which case the  
converter will continue regular operation. No protection is required  
in this case.  
However some DCM models require an increase to the minimum  
external output capacitor value in certain loading and trim  
condition. In applications where the load can go below 10ꢀ of rated  
load but the output trim is held constant, the range of output  
capacitor required is given by COUT-EXT-TRANS in the Electrical  
Specifications table. If the load can go below 10ꢀ of rated load and  
the DCM output trim is also dynamically varied, the range of output  
capacitor required is given by COUT-EXT-TRANS-TRIM in the Electrical  
Specifications table.  
Once the UVLO fault is detected by the fault protection logic, the  
converter shuts down and waits for the input voltage to rise above  
VIN-UVLO+. Provided the converter is still enabled, it will then restart.  
Input Overvoltage Fault Protection (OVLO)  
The converter’s input voltage is monitored to detect an input over  
voltage condition. When the input voltage is more than the  
VIN-OVLO+, a fault is detected, the powertrain stops switching, and the  
output voltage of the converter falls.  
After an OVLO fault occurs, the converter will wait for the input  
voltage to fall below VIN-OVLO-. Provided the converter is still enabled,  
the powertrain will restart.  
Light Load Boosting  
Under light load conditions, the DCM converter may operate in light  
load boosting depending on the line voltage. Light load boosting  
occurs whenever the internal power consumption of the converter  
combined with the external output load is less than the minimum  
power transfer per switching cycle. In order to maintain regulation,  
the error amplifier will switch the powertrain off and on repeatedly,  
to effectively lower the average switching frequency, and permit  
operation with no external load. During the time when the power  
train is off, the module internal consumption is significantly  
reduced, and so there is a notable reduction in no-load input power  
in light load boosting. When the load is less than 10ꢀ of rated Iout,  
the output voltage may rise by a maximum of 2.53 V, above the  
output voltage calculated from trim, temperature, and load  
line conditions.  
The powertrain controller itself also monitors the input voltage.  
Transient OVLO events which have not yet been detected by the fault  
sequence logic may first be detected by the controller if the input  
slew rate is sufficiently large. In this case, powertrain switching will  
immediately stop. If the input voltage falls back in range before the  
fault sequence logic detects the out of range condition, the  
powertrain will resume switching and the fault logic will not  
interrupt operation Regardless of whether the powertrain is running  
at the time or not, if the input voltage does not recover from OVLO  
before tOVLO, the converter fault logic will detect the fault.  
Output Undervoltage Fault Protection (UVP)  
The converter determines that an output overload or short circuit  
condition exists by measuring its primary sensed output voltage and  
the output of the internal error amplifier. In general, whenever the  
powertrain is switching and the primary-sensed output voltage falls  
below VOUT-UVP threshold, a short circuit fault will be registered. Once  
an output undervoltage condition is detected, the powertrain  
DCMDC-DC Converter  
Rev 1.0  
Page 18 of 23  