BCM384y120x1K5AC1
Reported Characteristics
Specifications apply over all line, load conditions, unless otherwise noted; Boldface specifications apply over the temperature range of -40°C ≤ TINTERNAL
≤ 125°C (T-Grade); All other specifications are at TINTERNAL = 25ºC unless otherwise noted.
Monitored Telemetry
• The BCM communication version is not intended to be used without a Digital Supervisor.
DIGITAL SUPERVISOR
PMBusTM READ COMMAND
UPDATE
RATE
ACCURACY
(RATED RANGE)
FUNCTIONAL
REPORTING RANGE
ATTRIBUTE
REPORTED UNITS
Input voltage
(88h) READ_VIN
(89h) READ_IIN
5% ( LL - HL )
5% ( 10 - 133% of FL)
5% ( LL - HL )
130 V to 450 V
- 0.85 A to 5.9 A
4.25 V to 14 V
100 µs
100 µs
100 µs
100 µs
100 ms
100 ms
VACTUAL = VREPORTED x 10-1
IACTUAL = IREPORTED x 10-3
VACTUAL = VREPORTED x 10-1
IACTUAL = IREPORTED x 10-2
RACTUAL = RREPORTED x 10-5
TACTUAL = TREPORTED
Input current
Output voltage[1]
Output current
Output resistance
Temperature[2]
(8Bh) READ_VOUT
(8Ch) READ_IOUT
5% ( 10 - 133% of FL )
5% ( 50 - 100% of FL)
7°C ( Full Range)
- 27 A to 190 A
1.0 mΩ to 3.0 mΩ
- 55ºC to 130ºC
(D4h) READ_ROUT
(8Dh) READ_TEMPERATURE_1
[1] Default READ Output Voltage returned when unit is disabled = -300 V.
[2] Default READ Temperature returned when unit is disabled = -273°C.
Variable Parameter
• Factory setting of all below Thresholds and Warning limits are 100% of listed protection values.
• Variables can be written only when module is disabled either EN pulled low or VIN < VIN_UVLO-
.
• Module must remain in a disabled mode for 3 ms after any changes to the below variables allowing ample time to commit changes to EEPROM.
FUNCTIONAL
REPORTING
RANGE
DIGITAL SUPERVISOR
PMBusTM COMMAND [3]
DEFAULT
VALUE
ACCURACY
(RATED RANGE)
ATTRIBUTE
CONDITIONS / NOTES
Input / Output Overvoltage
Protection Limit
VIN_OVLO- is automatically 3%
lower than this set point
(55h) VIN_OV_FAULT_LIMIT
(57h) VIN_OV_WARN_LIMIT
(D7h) DISABLE_FAULTS
(5Bh) IIN_OC_FAULT_LIMIT
(5Dh) IIN_OC_WARN_LIMIT
(4Fh) OT_FAULT_LIMIT
5% ( LL - HL )
5% ( LL - HL )
130 V to 435 V
130 V to 435 V
130 V or 260 V
0 to 5.25 A
100%
100%
100%
100%
100%
100%
100%
0 ms
Input / Output Overvoltage
Warning Limit
Input / Output Undervoltage
Protection Limit
Can only be disabled to a preset
default value
5% ( LL - HL )
Input Overcurrent
Protection Limit
5% ( 10 - 133% of FL)
5% ( 10 - 133% of FL)
7°C ( Full Range)
7°C ( Full Range)
50 µs
Input Overcurrent
Warning Limit
0 to 5.25 A
Overtemperature Protection
Limit
0 to 125°C
Overtemperature
Warning Limit
(51h) OT_WARN_LIMIT
(60h) TON_DELAY
0 to 125°C
Additional time delay to the
Undervoltage Startup Delay
Turn on Delay
0 to 100 ms
[3] Refer to Digital Supervisor datasheet for complete list of supported commands.
BCM® Bus Converter
Page 8 of 23
Rev 1.4
05/2015
vicorpower.com
800 927.9474