 浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第28页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第29页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第30页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第31页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第33页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第34页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第35页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第36页  
Multiple RPM-Based PWM Fan Controller for Five Fans  
Datasheet  
Bit 1 - DR_EXT_CLK - Enables the internal tachometer clock to be driven out on the CLK pin so that  
multiple devices can be synced to the same source.  
„
„
‘0’ (default) - The CLK pin acts as a clock input.  
‘1’ - The CLK pin acts as a clock output and is a push-pull driver.  
Bit 0 - USE_EXT_CLK - Enables the EMC2305 to use a clock present on the CLK pin as the  
tachometer clock. If the DR_EXT_CLK bit is set, then this bit is ignored and the device will use the  
internal oscillator.  
„
„
‘0’ (default) - The EMC2305 will use its internal oscillator for all Tachometer measurements.  
‘1’ - The EMC2305 will use the oscillator presented on the CLK pin for all Tachometer  
measurements.  
5.3  
Fan Status Registers  
Table 5.3 Fan Status Registers  
ADDR  
R/W  
REGISTER  
B7  
B6  
B5  
B4  
B3  
B2  
B1  
B0  
DEFAULT  
DRIVE_  
FAIL  
FAN_  
SPIN  
FAN_  
STALL  
24h  
R-C  
Fan Status  
WATCH  
-
-
-
-
00h  
Fan Stall  
Status  
FAN5_  
STALL  
FAN4_  
STALL  
FAN3_  
STALL  
FAN2_  
STALL  
FAN1_  
STALL  
25h  
26h  
27h  
R-C  
R-C  
R-C  
-
-
-
-
-
-
-
-
-
00h  
00h  
00h  
Fan Spin  
Status  
FAN5_  
SPIN  
FAN4_  
SPIN  
FAN3_  
SPIN  
FAN2_  
SPIN  
FAN1_  
SPIN  
Fan Drive  
Fail Status  
DRIVE_  
FAIL5  
DRIVE_  
FAIL4  
DRIVE_  
FAIL3  
DRIVE_  
FAIL2  
DRIVE_  
FAIL1  
The Fan Status registers contain the status bits associated with each fan driver.  
5.3.1  
Fan Status - 24h  
The Fan Status register indicates that one or more of the fan drivers has stalled or failed or that the  
Watchdog Timer has expired (see Section 4.8).  
Bit 7 - WATCH - Indicates that the Watchdog Timer has expired. When set, each fan is driven to 100%  
duty cycle and will remain at 100% duty cycle until they are programmed. This bit is cleared when it  
is read.  
Bit 2 - DRIVE_FAIL - Indicates that one or more fan drivers cannot meet the programmed fan speed  
at maximum PWM duty cycle. This bit is set when any bit in the Fan Drive Fail Status register is set  
and cleared when all bits in the Fan Drive Fail Status register are cleared.  
Bit 1 - FAN_SPIN - Indicates that one or more fan drivers cannot spin up. This bit is set when any bit  
in the Fan Spin Status register is set and cleared when all of the bits in the Fan Spin Status register  
are cleared.  
Bit 0 - FAN_STALL - Indicates that one or more fan drivers have stalled. This bit is set when any bit  
in the Fan Stall Status register is set and cleared when all of the bits in the Fan Stall Status register  
are cleared.  
5.3.2  
Fan Stall Status - 25h  
The Fan Stall Status register indicates which fan driver has detected a stalled condition (see  
Section 4.4.1). All bits are cleared upon a read if the error condition has been removed.  
Revision 1.1 (10-12-09)  
SMSC EMC2305  
DATA3S2HEET