415 V AC
Magnetic tripping limit
Limitation class
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
Contact position indicator
Control type
Local signalling
Mounting mode
Mounting support
9 mm pitches
Height
Width
Depth
Product weight
Colour
Mechanical durability
Electrical durability
Provision for padlocking
Connections - terminals
Wire stripping length
Tightening torque
8.5 x In +/- 20 % AC
12 x In +/- 20 % DC
3 conforming to EN/IEC 60947-2
500 V AC conforming to EN/IEC 60947-2
6 kV conforming to EN/IEC 60947-2
Yes
Toggle
ON/OFF indication
Clip-on
DIN rail
4
107 mm
36 mm
73 mm
0.22 kg
Grey
20000 cycles
10000 cycles
Padlockable
Tunnel type terminal, top or bottom rigid wire(s) 2.5...25 mm² max (AWG 14...AWG 4)
14 mm top or bottom
2.5 N.m top or bottom
Environment
Standards
UL 489
CSA C22.2 No 5
GB 14048.2
EN/IEC 60947-2
UL
CSA
CCC
IEC
IP40 for modular enclosure conforming to IEC 60529
IP20 conforming to IEC 60529
3 conforming to EN/IEC 60947-2
IV
2 conforming to IEC 60068-1
95 % 55 °C
2000 m
-30...70 °C
-40...80 °C
Product certifications
IP degree of protection
Pollution degree
Overvoltage category
Tropicalisation
Relative humidity
Operating altitude
Ambient air temperature for operation
Ambient air temperature for storage
Offer Sustainability
Sustainable offer status
RoHS (date code: YYWW)
REACh
Product environmental profile
Product end of life instructions
Green Premium product
Compliant - since 0627 - Schneider Electric declaration of conformity
Reference not containing SVHC above the threshold
Available
Need no specific recycling operations
2