型号: 60140
PDF下载: 下载PDF文件 查看货源
内容描述: [Thermal Magnetic Circuit Breaker, 2 Pole(s), 5A, 440VAC, 125VDC, Din-rail Mount,]
分类和应用: 电路保护
文件页数/大小: 3 页 / 104 K
品牌: SCHNEIDER [ SCHNEIDER ELECTRIC ]
 浏览型号60140的Datasheet PDF文件第2页浏览型号60140的Datasheet PDF文件第3页  
Product datasheet
Characteristics
60140
Multi 9 - C60 UL489 - MCB - 2P - 5 A - C Curve -
240 V - 10 kA - tunnel term
Main
Range
Product name
Product or component type
Device short name
Device application
Poles description
Number of protected poles
Neutral position
[In] rated current
Network type
Trip unit technology
Curve code
Breaking capacity
Multi 9
Multi 9 C60
Miniature circuit-breaker
C60 UL489
Distribution
2P
2
Left
5 A at 25 °C
AC
DC
Thermal-magnetic
C
Icu 6 kA at 440 V AC conforming to EN/IEC 60947-2
Icu 10 kA at 415 V AC conforming to EN/IEC 60947-2
Icu 20 kA at 240 V AC conforming to EN/IEC 60947-2
Icu 6 kA at 440 V AC conforming to GB 14048.2
Icu 10 kA at 415 V AC conforming to GB 14048.2
Icu 20 kA at 240 V AC conforming to GB 14048.2
AIR 10 kA at 240 V AC conforming to UL 489
AIR 10 kA at 125 V DC conforming to UL 489
Icu 10 kA at 125 V DC conforming to EN/IEC 60947-2
Icu 10 kA at 125 V DC conforming to GB 14048.2
AIR 10 kA at 240 V AC conforming to CSA C22.2 No 5.2
AIR 10 kA at 125 V DC conforming to CSA C22.2 No 5.2
Yes conforming to EN/IEC 60947-2
Suitability for isolation
Complementary
Network frequency
[Ue] rated operational voltage
50/60 Hz
125 V DC
240 V AC
440 V AC