欢迎访问ic37.com |
会员登录 免费注册
发布采购

SA2005MPA 参数 Datasheet PDF下载

SA2005MPA图片预览
型号: SA2005MPA
PDF下载: 下载PDF文件 查看货源
内容描述: 引脚可选三相功率/电能计量芯片的步进电机/脉冲计数器的应用与防篡改功能 [Pin Selectable Three Phase Power / Energy Metering IC for Stepper Motor / Impulse Counter Applications with Anti Tamper Features]
分类和应用: 计数器脉冲光电二极管电机
文件页数/大小: 12 页 / 361 K
品牌: SAMES [ SAMES ]
 浏览型号SA2005MPA的Datasheet PDF文件第4页浏览型号SA2005MPA的Datasheet PDF文件第5页浏览型号SA2005MPA的Datasheet PDF文件第6页浏览型号SA2005MPA的Datasheet PDF文件第7页浏览型号SA2005MPA的Datasheet PDF文件第9页浏览型号SA2005MPA的Datasheet PDF文件第10页浏览型号SA2005MPA的Datasheet PDF文件第11页浏览型号SA2005MPA的Datasheet PDF文件第12页  
SA2005M  
ssaammeess  
TYPICAL APPLICATION  
Voltage Divider  
The analog (metering) interface described in this section is  
designed for measuring 230V/60A with precision better than  
Class1.  
The voltage divider for phase one is calculated for a voltage  
drop of 14V. Equations for the voltage divider in figure 4 are:  
RB = R20 + R23 + R26  
RB = R12 || (R17 + P1)  
The most important external components for the SA2005M  
integrated circuit are the current sense resistors, the voltage  
sense resistors and the bias setting resistor. The resistors  
used in the metering section should be of the same type so  
temperatureeffectsareminimized.  
A 5k trimpot will be used in the voltage channel for meter  
calibration. The center position on the pot is used in the  
calibration P1 = 2.5kW.  
Combining the two equations gives:  
(RA + RB ) / 230V = RB / 14V  
CurrentInputIIN1, IIP1, IIN2, IIP2  
Two current transformers are used to measure the current in  
the live and neutral phases. The output of the current  
transformer is terminated with a low impedance resistor. The  
voltage drop across the termination resistor is converted to a  
current that is fed to the differential current inputs of the  
SA2005M.  
Values for resistors R17 = 22kW, P1 = 2.5kW and R12 = 1MW  
is chosen.  
Substituting the values result in:  
RB = 23.914kW  
RA = RB x ( 230V / 14V – 1 )  
RA = 368.96kW.  
CT Termination Resistor  
The voltage drop across the CT termination resistor at rated  
current should be at least 20mV. The CTs have low phase shift  
and a ratio of 1:2500. The CT is terminated with a 3.6W resistor  
giving a voltage drop of 86.4mV across the termination resistor  
Standard resistor values for R24, R25 and R26 are chosen to  
be 130kW.  
atratedconditions(I forthemeter).  
max  
Standard resistor values for R18, R19, R20, R21, R22 and  
R23 are chosen to be 120kW.  
CurrentSensorInputResistors  
The resistors R1 and R2 define the current level into the  
current sense inputs of phase one of the SA2005M. The  
resistor values are selected for an input current of 16µA on the  
current inputs of the SA2005M at rated conditions. For a 60A  
meter at 2500:1 CT the resistor values are calculated as  
follows:  
The capacitor C1 is used to compensate for phase shift  
between the voltage sense inputs and the current sense inputs  
of the device, in cases where CTs with phase errors are used.  
The phase shift caused by the CT may be corrected by  
inserting a capacitor in the voltage divider circuit. To  
compensate for a phase shift of 0.18 degrees the capacitor  
value is calculated as follows:  
R1=R2 =(I /1A)xR /2  
SH  
L
=60A/2500/1Ax3.6W /2  
= 2.7kW  
C = 1 / (2 xp x Mains frequency x R12 x tan (Phase shift angle))  
C = 1 / ( 2 xp x 50 x 1MW x tan (0.18 degrees ))  
C = 1.013µF  
I =Linecurrent  
L
RSH=CTTerminationresistor  
2500=CTratio  
Reference Voltage Bias resistor  
R7 defines all on chip and reference currents. With R7 = 24kW  
optimum conditions are set. Device calibration is done on the  
voltage input of the device.  
The three current channels are identical so R1 = R2 = R3 =  
R4=R5=R6.  
VoltageInputIVP  
Device setup  
The voltage input of the SA2005M (IVP) is driven with a current  
of 14µA at nominal mains voltage. This voltage input saturates  
at approximately 17µA. At a nominal voltage current of 14µA  
allows for 20% overdriving. The mains voltage is divided with a  
voltage divider to 14V that is fed to the voltage input pins via a  
1MW resistor.  
The resistor values calculated above is for a 60A rated meter  
so RA must be set to VDD, according to the description under  
Input Signals. The RE and IM inputs of the device must be set  
to the appropriate states for the meter to function correctly.  
8/12  
http://www.sames.co.za