Resolution(RE)  
Current Sense Inputs (IIN1, IIP1, IIN2, IIP2, IIN3, IIP3)  
The current sense inputs connects to a termination resistor  
connected across the terminals of a current transformer. At  
rated current the resistor values should be selected for input  
The RE input selects the summing mode for the programmable  
adder as well as the dividing ratio for the LED output (LED  
resolution). Thefollowingtableliststheoptionsavailable:  
currents of 16µA . Referring to figure 8, the resistors R1 and  
RMS  
RE Pin  
Summing Mode  
Dividing Ratio  
R2 on current channel 1, resistors R3 and R4 on current  
channel 2 and resistors R5 and R6 on current channel 3, define  
the current level into the current sense inputs of the SA2005M.  
The current sense inputs saturates at an input current of  
±25µA peak. Resistors R29, R30 and R31 are used as current  
transformer termination resistors. The voltage drop across the  
termination resistors should be at least 20mV at rated  
conditions. Values for the current sense inputs are calculated  
as follows:  
(LED Resolution)  
VSS  
Total sum  
1
4
1
4
PH/DIR  
OPEN  
VDD  
Total sum  
Absolute sum  
Absolute sum  
The summing mode is the representation of the measured  
energyandcanbeeitherofthefollowingtypes:  
R1  
R3  
R5  
= R  
= R  
= R  
2
= ( I  
= ( I  
= ( I  
L/ 16µARMS) x R29/ 2  
4
6
L
L
/ 16µARMS ) x R30 / 2  
/ 16µARMS ) x R31 / 2  
Totalsum  
This represents the total sum of the energy measured on all  
three phases flowing through the current sensors. Negative  
energyflowistakenintoconsideration.  
Where:  
I = Line current/CT-ratio  
L
The value of the termination resistors should be less than the  
resistance of the CT's secondary winding.  
Absolutesum  
This represents the sum of the energy measured on all three  
phases, regardless of the direction of energy flow through the  
currentsensors.  
Voltage Reference Connection (VREF)  
A bias resistor of 24kW provides an optimum bias conditions on  
chip. Calibration of the SA2005M is done on the voltage sense  
inputs as described in the Typical Application.  
Impulses(IM)  
The IM inputs selects between 1, 10, or 100 dividing ratio for  
the motor drive outputs (counter resolution). Please note that  
the device will not perform metering functions while in test  
mode. Refer to the Using the RA, Re, Im inputs section for  
furtherinformation.  
Rated (RA)  
The rated condition select pin allows the metering constants  
(LED output and Motor Drive output) to remain unchanged for  
different rated conditions having a 1:2:3 scaling ratio, for  
example 230V/20A, 230V/40A and 230V/60A. This option  
allows for the development of different rated meters requiring  
minimal changes. The only changes to be implemented is the  
selection of the current sense resistors for the expected rated  
load currents and the selection of pins RA, RE and IM.  
IM Pin  
VSS  
PH/DIR  
VDD  
Dividing Ratio (Counter Resolution)  
100 (1P/KwH)  
10 (10P/KwH)  
1 (100P/KwH)  
OPEN  
Test Mode  
RA Pin Rated Conditions Multiplying Ratio  
1/3  
2/3  
3/3  
VSS  
Test Inputs (TEST)  
PH/DIR  
VDD  
The TEST input is the manufacturers test pin and must be  
connectedtoVSSinameteringapplication.  
Fast LED output. The output is 1252Hz at rated  
current and voltage inputs.  
Open  
At a rated condition of 230V/60A (13800W), setting the RA pin  
to VDD (ratio set to 3/3) and the RE pin to VSS (LED  
resolution) the LED pulse rate will be 3200 pulses/KWh. With a  
combination of RA, RE and IM settings various rated condition  
can easily be met. Refer to the Using the RA, RE, IM inputs  
sectionforfurtherinformation.  
5/12  