1. INTENDED USE  
This device is designed for installation in an enclosure and is intended for the general use such as in industrial control,  
office, communication, and instrumentation equipment.  
Do not use this power supply in equipment, where malfunction may cause severe personal injury or threaten human  
life.  
This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations.  
2. INSTALLATION REQUIREMENTS  
This device may only be installed and put into operation by qualified personnel.  
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.  
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to  
the factory for inspection.  
Mount the unit on a DIN-rail so that the output terminals are located on the top and the input terminals are located  
on the bottom of the unit. For other mounting orientations see de-rating requirements in this document. See chapter  
22.13.  
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do  
not cover ventilation grid (e.g. cable conduits) by more than 30%!  
Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are  
recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance  
to 15mm in case the adjacent device is a heat source (e.g. another power supply).  
A disconnecting means shall be provided for the output of the power supplies when used in applications according to  
CSA C22.2 No 107.1-01.  
WARNING  
Risk of electrical shock, fire, personal injury or death.  
- Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for  
earth connection and not one of the screws on the housing.  
- Turn power off before working on the device. Protect against inadvertent re-powering.  
- Make sure that the wiring is correct by following all local and national codes.  
- Do not modify or repair the unit.  
- Do not open the unit as high voltages are present inside.  
- Use caution to prevent any foreign objects from entering the housing.  
- Do not use in wet locations or in areas where moisture or condensation can be expected.  
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.  
Notes for use in hazardous location areas:  
The power supply is suitable for use in Class I Division 2 Groups A, B, C, D locations.  
Additionally, the QS20.241-A1 is suitable for use in Group II Category 3 (Zone 2) environments and is evaluated  
according to EN 60079-0:2009 and EN 60079-15:2010.  
WARNING EXPLOSION HAZARDS!  
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the  
voltage adjustment unless power has been switched off or the area is known to be non-hazardous.  
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the  
requirements of the EN 60079-15.  
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN  
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.  
3/26  
www.pulspower.com Phone +49 89 9278 0 Germany  
 
 