 浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第29页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第30页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第31页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第32页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第33页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第34页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第36页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第37页  
Precautions for Correct Use  
Installation Environment  
Do not install the ZEN in the following locations.  
Locations subject to radical changes in temperature  
Locations with high humidity subject to condensation  
Locations subject to excessive dust or dirt  
Locations subject to corrosive gas  
Locations subject to direct sunlight  
Do not install the ZEN in locations subject to shock or vibration.  
Extended use in such locations may cause damage from stress.  
In environments subject to static electricity (e.g., close to pipes  
conveying forming materials, powders, or fluid materials), separate  
the ZEN as far as possible from the source of static electricity.  
The ZEN is neither waterproof nor oil-proof. Do not use it in  
locations subject to water or oil.  
Use the ZEN within the allowable power supply voltage range. Be  
particularly careful in locations with bad power supply conditions,  
e.g., large fluctuations in the power supply voltage.  
Do not install the ZEN in locations subject to excessive noise,  
which may cause the ZEN to fail.  
Take appropriate and sufficient countermeasures when installing  
systems in the following locations:  
Locations subject to strong electromagnetic fields  
Locations subject to possible exposure to radioactivity  
Power Supply  
Always turn OFF the power supply to the ZEN before attempting  
any of the following.  
Assembling the ZEN  
Connecting or disconnecting any cables or wiring  
Attaching or removing the Memory Cassette  
Attaching or removing the Battery Unit  
If the power supply is interrupted for two days or more (at 25°C),  
the internal capacitor will discharge and internal bit status and the  
contents of PV areas will be lost or corrupted and dates and times  
will be reset. When restarting operation after the power supply has  
been interrupted for an extended period of time, check the system  
in advance to confirm that no errors will occur.  
Handling  
Connect connectors only after confirming that the direction or  
polarity is correct.  
Failures could result if dust or dirt enters the ZEN. Always connect  
the connector cover to the computer connector whenever it is not  
being used.  
Do not remove the label from the left side of the CPU Unit if a  
Battery Unit is not mounted.  
Other  
The execution of the ladder program in the ZEN is different from  
that for other PLCs. Refer to “Difference between ZEN  
Programmable Relays and PLC Ladder Program Execution” on  
page 33.  
Abide by all local ordinances and regulations when disposing of the  
ZEN.  
The Battery Unit (ZEN-BAT01, sold separately) contains a lithium  
battery. Observe all applicable legal requirements for your area  
when disposing of the lithium battery.  