 浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第25页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第26页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第27页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第28页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第30页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第31页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第32页浏览型号ZEN-STARTER02-V2的Datasheet PDF文件第33页  
Precautions when Switching from Previous Units  
Previous models of Expansion I/O Units cannot be connected to V2 CPU Units.  
ZEN-8E1@R Expansion I/O Units with relay outputs need to be connected to a power supply.  
A ZEN-@C@D@-D-V2 CPU Unit with DC power supply cannot be connected to an Expansion I/O Unit with AC inputs.  
When connecting Expansion I/O Units with DC inputs to a CPU Unit with an AC power supply, the burst noise immunity will be 1 kV (IEC 61000-  
4-4).  
There is no change to the 8 A per contact for relay output, but the total output for all contacts must be as follows:  
Units with 10 I/O Points: 20 A max. (15 A max. for Communications-type CPU Units)  
Units with 20 I/O Points: 40 A max.  
Expansion I/O Units:  
20 A max.  
Always use the ZEN-SOFT01-V4 Support Software for V2 CPU Units.  
Input wiring for CPU Units with DC power supplies differs from that for Pre-V1 CPU Units. Refer to the following diagrams.  
V2 and V1 CPU Units  
Pre-V1 CPU Units  
The input circuit common terminal is connected  
internally to the negative () side of the power  
supply circuit.  
COM wiring depends on whether a negative common or positive common is being used.  
Positive (+) COM Wiring  
Negative () COM Wiring  
24 VDC  
24 VDC  
COM wiring required.  
24 VDC  
COM wiring required.  
Analog inputs possible.  
Analog inputs possible.  
Input  
devices  
Input  
devices  
Input  
devices  
COM  
+
COM  
+
NC  
+
CPU Unit with 10 I/O Points  
CPU Unit with 10 I/O Points  
CPU Unit with 10 I/O Points  
Note: I4 and I5 (Ia and Ib for CPU Units with 20 I/O  
points) cannot be used as analog input terminals.  
Changes  
Ratings and Specifications  
CPU Units  
Item  
V2 Units  
V1 Units  
Pre-V1 Units  
Rated power  
Models with DC  
10.8 to 28.8 VDC  
20.4 to 26.4 VDC  
supply voltage power supply  
Power  
Models with AC  
See Ratings on page 7.  
30 VA max.  
(with 3 Expansion I/O Units connected)  
consumption power supply  
Models with DC  
power supply  
6.5 W max.  
(with 3 Expansion I/O Units connected)  
Inrush current Models with AC  
power supply  
Models with 10 I/O points: 4.5 A max.  
Models with 20 I/O points: 4.5 A max.  
40 A max.  
Models with DC  
power supply  
Models with 10 I/O points: 30 A max.  
Models with 20 I/O points: 30 A max.  
20 A max.  
DC inputs  
I0 to I3  
(See note 1.)  
Input impedance 5.3 kΩ  
5 kΩ  
4.8 kΩ  
ON voltage  
8 VDC min.  
16 VDC min.  
Input common  
Independent common terminal  
Internally connected to  
power supply terminal  