CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@
●Transistor Outputs (Sinking or Sourcing)
Specification
Item
CP1W-40EDT
CP1W-40EDT1
CP1W-32ET
CP1W-32ET1
CP1W-20EDT
CP1W-20EDT1
CP1W-16ET
CP1W-16ET1
CP1W-8ET
CP1W-8ET1
4.5 to 30 VDC
0.3 A/output
4.5 to 30 VDC
0.3 A/output
24 VDC +10%/-5%
0.3 A/output
4.5 to 30 VDC
0.3 A/output
4.5 to 30 VDC
0.3 A/output
Max. switching capacity
*1
0.9 A/common
3.6 A/Unit
0.9 A/common
7.2 A/Unit
0.9 A/common
1.8 A/Unit
0.9 A/common
3.6 A/Unit
0.9 A/common
1.8 A/Unit
Leakage current
Residual voltage
ON delay
0.1 mA max.
1.5 V max.
0.1 mA max.
1.5 V max.
0.1 mA max.
1.5 V max.
0.1 ms.
0.1 mA max.
1.5 V max.
0.1 mA max.
1.5 V max.
0.1 ms max.
0.1 ms max.
0.1 ms max.
0.1 ms max.
1 ms max.
1 ms max.
1 ms max.
1 ms max.
1 ms max.
OFF delay
24 VDC +10%/-5%
5 to 300 mA
24 VDC +10%/-5%
5 to 300 mA
24 VDC +10%/-5%
5 to 300 mA
24 VDC +10%/-5%
5 to 300 mA
24 VDC +10%/-5%
5 to 300 mA
Max. number of
Simultaneously ON
Points of Output
16 pts (100%)
1 fuse/common
24 pts (75%)
8 pts (100%)
16 pts (100%)
8 pts (100%)
Fuse *2
Sinking Outputs
Sourcing Outputs
Output LED
Output LED
OUT
L
COM (+)
Circuit configuration
L
Internal
circuits
Internal
circuits
24 VDC/4.5
to 30 VDC
OUT
24 VDC/4.5
to 30 VDC
OUT
L
COM (−)
L
OUT
*1 If the ambient temperature is maintained below 50°C, up to 0.9 A/common can be used.
(A)
0.9
0.8
0
50 55
(°C)
Ambient temperature
*2 The fuse cannot be replaced by the user. Replace the Unit if the fuse breaks due to an short-circuit or overcurrent.
*3 Do not connect a load to an output terminal or apply a voltage in excess of the maximum switching capacity.