Compact Plug-in Models (8-pin Type)  
Specifications  
Item  
General-purpose  
Controller  
Long-distance  
Controllers  
High-sensitivity  
Controllers  
Low-sensitivity  
Controller  
Two-wire  
Variable  
Sensitivity  
Controller  
Controller  
61F-GP-N8  
61F-GP-N8Y  
(see note 4)  
61F-GP-N8L 2KM  
(for 2 km)  
61F-GP-N8L 4KM  
(for 4 km)  
61F-GP-N8H  
61F-GP-N8HY  
(see note 4)  
61F-GP-N8D  
61F-GP-N8R  
61F-GP-N8-V50  
Controlling mate- For control of ordi- For control of ordi- For control of liq-  
For control of liq-  
For control of ordi- For control of cases  
rials and operat- nary purified water nary purified water uids with high spe- uids with low spe- nary purified water where variable sen-  
ing conditions  
or sewage water  
in cases where the cific resistance  
distance between such as distilled  
sewage pumps and water  
water tanks or be-  
cific resistance  
such as salt water, used in combina-  
sewage water, acid tion with Two-wire detectionoffrothon  
chemicals, alkali  
chemicals  
or sewage water  
sitivity control is re-  
quired such as  
Electrode Holder  
(incorporating a re- uid, control of soil  
the surface of a liq-  
tween receiver  
tanks and supply  
tanks is long or  
where remote con-  
trol is required.  
sistor of 6.8 kΩ)  
moisture content,  
or detection of de-  
gree of water pollu-  
tion  
Supply voltage  
24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz  
24, 110, 220 or  
240 VAC; 50/60 Hz  
Operatingvoltage 85% to 110% of rated voltage  
range  
Interelectrode  
voltage  
8 VAC  
24 VAC  
8 VAC  
24 VAC  
Interelectrode  
current  
Approx. 1 mA AC max.  
Approx.  
0.4 mA AC max.  
Approx. 1 mA AC max.  
Approx. 3 mA AC  
max.  
Power consump- Approx. 3.5 VA max.  
tion  
Interelectrode op- 0 to approx. 4 kΩ  
erate resistance  
0 to 1.3 kΩ (for  
2 km)  
0 to 0.5 kΩ (for  
4 km)  
Approx. 15 kΩ to  
approx. 70 kΩ  
(see note 3)  
0 to approx. 1.3 kΩ 0 to approx. 2 kΩ  
0 to 50 kΩ (Vari-  
able)  
Interelectrode re- Approx. 15 k to ∞ Ω 4 k to ∞ Ω  
Approx. 300 k to  
∞ Ω  
Approx. 4 k to ∞ Ω Approx. 15 k to ∞ Ω Operating resis-  
tance +50 kΩ max.  
lease resistance  
(for 2 km)  
2.5 k to ∞ Ω  
(for 4 km)  
Response time  
Operate: 80 ms max.  
Release: 160 ms max.  
1 km max. 2 km max.  
4 km max.  
Cable length  
(see note 1)  
50 m max.  
1 km max.  
800 m max.  
50 m max.  
Control output  
1 A, 250 VAC (Inductive load: cosφ = 0.4)  
3 A, 250 VAC (Resistive load)  
Ambient tempera- Operating: –10 to 55°C  
ture  
Ambient humidity Operating: 45% to 85% RH  
Insulation resis- 100 MΩ min. (at 500 VDC)  
tance  
(see note 2)  
Dielectric  
strength  
2000 VAC, 50/60 Hz for 1 min.  
(see note 2)  
Life expectancy  
Electrical: 100,000 operations min.  
Mechanical: 5,000,000 operations min.  
Weight  
Approx. 155 g  
Accessories  
Hold-down clip PFC-N8  
Note: 1. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as  
the cable diameter or number of conductors becomes larger.  
2. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power ter-  
minals and contact terminals, and between Electrode terminals and contact terminals.  
3. Possible to use with 15 kΩ or less, however, this may cause reset failure.  
4. 61F-GP-N8H/-N8Y High-sensitivity Controllers use advanced operation.  
When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter-  
nal relay will not operate.  
When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal  
relay will operate.  
If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation.  
9