61F-GP-N@
■ Compact Plug-in Models (8-pin Type)
Specifications
Item
General-purpose
Controller
Long-distance
Controllers
High-sensitivity
Controllers
Low-sensitivity
Controller
Two-wire
Variable
Sensitivity
Controller
Controller
61F-GP-N8
61F-GP-N8Y
(see note 4)
61F-GP-N8L 2KM
(for 2 km)
61F-GP-N8L 4KM
(for 4 km)
61F-GP-N8H
61F-GP-N8HY
(see note 4)
61F-GP-N8D
61F-GP-N8R
61F-GP-N8-V50
Controlling mate- For control of ordi- For control of ordi- For control of liq-
For control of liq-
For control of ordi- For control of cases
rials and operat- nary purified water nary purified water uids with high spe- uids with low spe- nary purified water where variable sen-
ing conditions
or sewage water
in cases where the cific resistance
distance between such as distilled
sewage pumps and water
water tanks or be-
cific resistance
such as salt water, used in combina-
sewage water, acid tion with Two-wire detectionoffrothon
chemicals, alkali
chemicals
or sewage water
sitivity control is re-
quired such as
Electrode Holder
(incorporating a re- uid, control of soil
the surface of a liq-
tween receiver
tanks and supply
tanks is long or
where remote con-
trol is required.
sistor of 6.8 kΩ)
moisture content,
or detection of de-
gree of water pollu-
tion
Supply voltage
24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz
24, 110, 220 or
240 VAC; 50/60 Hz
Operatingvoltage 85% to 110% of rated voltage
range
Interelectrode
voltage
8 VAC
24 VAC
8 VAC
24 VAC
Interelectrode
current
Approx. 1 mA AC max.
Approx.
0.4 mA AC max.
Approx. 1 mA AC max.
Approx. 3 mA AC
max.
Power consump- Approx. 3.5 VA max.
tion
Interelectrode op- 0 to approx. 4 kΩ
erate resistance
0 to 1.3 kΩ (for
2 km)
0 to 0.5 kΩ (for
4 km)
Approx. 15 kΩ to
approx. 70 kΩ
(see note 3)
0 to approx. 1.3 kΩ 0 to approx. 2 kΩ
0 to 50 kΩ (Vari-
able)
Interelectrode re- Approx. 15 k to ∞ Ω 4 k to ∞ Ω
Approx. 300 k to
∞ Ω
Approx. 4 k to ∞ Ω Approx. 15 k to ∞ Ω Operating resis-
tance +50 kΩ max.
lease resistance
(for 2 km)
2.5 k to ∞ Ω
(for 4 km)
Response time
Operate: 80 ms max.
Release: 160 ms max.
1 km max. 2 km max.
4 km max.
Cable length
(see note 1)
50 m max.
1 km max.
800 m max.
50 m max.
Control output
1 A, 250 VAC (Inductive load: cosφ = 0.4)
3 A, 250 VAC (Resistive load)
Ambient tempera- Operating: –10 to 55°C
ture
Ambient humidity Operating: 45% to 85% RH
Insulation resis- 100 MΩ min. (at 500 VDC)
tance
(see note 2)
Dielectric
strength
2000 VAC, 50/60 Hz for 1 min.
(see note 2)
Life expectancy
Electrical: 100,000 operations min.
Mechanical: 5,000,000 operations min.
Weight
Approx. 155 g
Accessories
Hold-down clip PFC-N8
Note: 1. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as
the cable diameter or number of conductors becomes larger.
2. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power ter-
minals and contact terminals, and between Electrode terminals and contact terminals.
3. Possible to use with 15 kΩ or less, however, this may cause reset failure.
4. 61F-GP-N8H/-N8Y High-sensitivity Controllers use advanced operation.
When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter-
nal relay will not operate.
When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal
relay will operate.
If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation.
9