61FGPNL2KM 参数 Datasheet PDF下载

61FGPNL2KM图片预览
型号: 61FGPNL2KM
PDF下载: 下载PDF文件 查看货源
内容描述: [Floatless Level Switch]
分类和应用:
文件页数/大小: 15 页 / 1104 K
品牌: OMRON [ OMRON ELECTRONICS LLC ]
 浏览型号61FGPNL2KM的Datasheet PDF文件第3页浏览型号61FGPNL2KM的Datasheet PDF文件第4页浏览型号61FGPNL2KM的Datasheet PDF文件第5页浏览型号61FGPNL2KM的Datasheet PDF文件第6页浏览型号61FGPNL2KM的Datasheet PDF文件第8页浏览型号61FGPNL2KM的Datasheet PDF文件第9页浏览型号61FGPNL2KM的Datasheet PDF文件第10页浏览型号61FGPNL2KM的Datasheet PDF文件第11页  
61F-GP-N@  
Two-Wire Connections  
Automatic Water Supply and Drainage Control  
Compact, Plug-in Type  
61F-GP-NR  
Dimensions:  
page 14  
Automatic Water Supply Control  
Automatic Drainage Control  
Connections  
Connections  
Commercial Voltage  
Commercial Voltage  
R S  
T
R S T  
61F-GP-NR  
61F-GP-NR  
5
4
5
4
MCCB  
MCCB  
Control  
circuit  
Control  
circuit  
0 V  
0 V  
24 V  
24 V  
U
U
Power  
supply  
Power  
supply  
8 V  
U
8 V  
U
3
9
2
3
9
2
10  
11  
1
10  
11  
1
Contac-  
tor  
Contac-  
tor  
(See note.)  
PS-3SR  
(See note.)  
R
Motor  
Motor  
Waste-  
water  
tank  
protection  
relay  
protection  
relay  
Stop  
Start  
R
PS-3SR  
Water  
tank  
Water supply  
source  
E1  
E2  
E3  
E1  
E2  
E3  
M
P
M
P
Reservoir  
Note: Be sure to ground the common Electrode E3 (the  
longest Electrode).  
Note: Be sure to ground the common Electrode E3 (the  
longest Electrode).  
Connection Sockets  
Connection Sockets  
PF113 (Front-connecting)  
PL11 (Rear-connecting)  
PF113 (Front-connecting)  
PL11 (Rear-connecting)  
Connect terminal 1 to the contactor’s coil terminal.  
Connect terminal 11 to the contactor’s coil terminal.  
Note: The power supply depends on the specifications of the  
Note: The power supply depends on the specifications of the  
model.  
model.  
With 2-wire connections, only two wires are required between  
the 61F-GP-NR and Electrode Holder, but three wires are  
required for the Electrodes.  
With 2-wire connections, only two wires are required between  
the 61F-GP-NR and Electrode Holder, but three wires are  
required for the Electrodes.  
The Electrode Holder must be specified for 2-wire connections.  
(Resistance R is built into Electrode Holders for 2-Wire  
Connections.)  
The Electrode Holder must be specified for 2-wire connections.  
(Resistance R is built into Electrode Holders for 2-Wire  
Connections.)  
Principles of Operation  
Principles of Operation  
Water  
supply  
P
(Indicator ON)  
(Indicator ON)  
Pump ON  
E1  
Pump OFF  
Pump ON  
E1  
Pump OFF  
(Indicator OFF)  
P
(Indicator OFF)  
E2  
E2  
E3  
E3  
Water drainage  
The pump stops when the water level reaches E1 (indicator ON)  
and starts when the water level drops below E2 (indicator OFF).  
The pump starts when the water level reaches E1 (indicator ON)  
and stops when the water level drops below E2 (indicator OFF).  
7