Specifications
I
Ratings and Characteristics
Model/Items
General-purpose
Controller
61F-GP-N8
Long-distance
Controllers
61F-GP-N8L 2KM
(for 2 km)
61F-GP-N8L 4KM
(for 4 km)
High-sensitivity
Controllers
61F-GP-N8H
61F-GP-N8HY
(see note 1)
For control of liquids
with high specific re-
sistance such as dis-
tilled water
Low-sensitivity
Controller
61F-GP-N8D
Two-wired
Controller
61F-GP-N8R
Controlling materials and
operating conditions
For control of ordinary For control of ordinary
purified water or sew- purified water in cas-
age water
es where the distance
between sewage
pumps and water
tanks or between re-
ceiver tanks and sup-
ply tanks is long or
where remote control
is required.
85% to 110% of rated voltage
8 VAC
Approx. 1 mA AC max.
Approx. 3.5 VA max.
Approx. 0 to 4 kΩ
Approx. 0 to 1.3 kΩ
(for 2 km)
Approx. 0 to 0.5 kΩ
(for 4 km)
For control of liquids
with low specific re-
sistance such as salt
water, sewage water,
acid chemicals, alkali
chemicals
For control of ordinary
purified water or sew-
age water used in
combination with two-
wired-type electrode
holder (incorporating
a resistor of 6.8 kΩ)
Operating voltage range
Interelectrode voltage
Interelectrode current
Power consumption
Interelectrode operate
resistance
24 VAC
Approx.
0.4 mA AC max.
Approx. 15 kΩ to
70 kΩ
(see note 3)
8 VAC
Approx. 1 mA AC max.
Approx. 0 to 1.3 kΩ
Approx. 0 to 2 kΩ
Interelectrode release
resistance
Approx. 15 k to
∞ Ω
Approx. 4 k to
∞ Ω
(for Approx. 300 k to
∞ Ω
Approx. 4 k to
∞ Ω
2 km)
Approx. 2.5 k to
∞ Ω
(for 4 km)
Approx. 15 k to
∞ Ω
Response time
Cable length
(see note 2)
Control output
Ambient temperature
Ambient humidity
Insulation resistance
(see note 3)
Dielectric strength
(see note 4)
Life expectancy
Operate: 80 ms max.
Release: 160 ms max.
1 km max.
2 km max.
4 km max.
50 m max.
1 km max.
800 m max.
1 A, 250 VAC (Inductive load: cosφ = 0.4)
3 A, 250 VAC (Resistive load)
Operating:
−10°C
to 55°C
Operating: 45% to 85% RH
100 MΩ max. (at 500 VDC)
2000 VAC, 50/60 Hz for 1 min.
Electrical:
100,000 operations min.
Mechanical: 5,000,000 operations min.
Note: 1.
The relay in the 61F-GP-N8H de-energizes when there is water present across the electrodes, whereas the relay in the 61F-GP-N8HY
energizes when there is water present across the electrodes.
2.
The length when using completely-insulated, 600-V, 3-conductor (0.75 mm
2
) cabtyre cables. Usable cable lengths will become shorter
as the cable diameter or number of conductors becomes larger.
3.
The insulation resistance and dielectric strength indicate values between power terminals and electrode terminals, between power ter-
minals and contact terminals, and between electrode terminals and contact terminals.
4.
Possible to use with 10 kΩ or less, however, this may cause reset failure.
Conductive Level Controller
61F-GP-N8
E-7
Level
Controllers
Supply voltage
24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz