61F-D21T-V1
Ordering Information
■
List of Models
Conductive Level Controller
Supply voltage
24 VAC/DC
Model
61F-D21T-V1 24 VAC/DC
100 to 240 VAC
61F-D21T-V1 100 to 240 VAC
Specifications
Rated voltage
Operating voltage range
Voltage between electrodes
Power consumption
24 VAC, 50/60 Hz, or 24 VDC
100 to 240 VAC, 50/60 Hz
85% to 110% of rated voltage
6 V p-p (approx. 20 Hz)
24 VDC: 2 W max.
24 VAC: 4 VA max.
100 to 240 VAC: 5 VA max.
10 kΩ to 100 kΩ (variable)
250 kΩ max.
Approx. 0.1 to 10 s (variable)
100 m max. with completely insulated (600 V) cabtire cable with 3 conductors (0.75 mm
2
)
6 A at 250 VAC for resistive load at 20°C, 1 A at 250 VAC for inductive load cosφ = 0.4 at 20°C
Green LED: Power, Yellow LED: Control output
Operating:
−20
to 60°C, Storage:
−30
to 70°C (with no condensation or icing)
Operating: 25% to 85%, Storage: 25% to 85%
2,000 m max.
100 MΩ min. (at 500 VDC) between power supply section, electrode section, and contact section
2,000 VAC 50/60 Hz for 1 min between power source section, electrode section, and contact section
Vibration of 10 to 55 Hz and acceleration of 50 m/s
2
for 5 min. 10 times each in X, Y, and Z directions
100 m/s
2
3 times each in 6 directions on 3 axes
Overvoltage Category II, Pollution Degree 2
EN61010-1
EN61326 Industrial applications
Operating resistance
Reset resistance
Response time
Cable length
Control output
Indicators
Ambient temperature
Ambient humidity
Elevation
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Installation environment
Safety standards
EMC
2