Racks  
Section 2-2  
2-2-3 Expansion I/O Racks  
Expansion I/O Racks, shown in the following diagram, can be used to expand  
the CV-series PCs. There are five models of Expansion I/O Backplane that can  
be used, as shown in the following table. These vary in the number of slots that  
they provide for Units (other than the Power Supply Unit and I/O Interface Unit)  
and in expansion capabilities. CV500 Expansion I/O Backplanes offer complete  
expansion capabilities, while CVM1 Expansion I/O Backplanes do not support  
I/O Interface Units and thus must be connected directly to the CPU Backplane  
(see Single Expansion I/O Rack in this subsection).  
Expansion I/O  
Backplane  
No. of slots  
I/O Interface Unit  
CV500-BI042  
CV500-BI062  
CV500-BI112  
CVM1-BI064  
CVM1-BI114  
4
6
Yes  
Yes  
Yes  
No  
11  
6
11  
No  
An Expansion I/O Rack can be connected either directly to the CPU Backplane  
(seeSingle Expansion I/O Rack in this subsection) or to an I/O Control Unit.Up to  
seven Expansion I/O Racks can be connected to the I/O Control Unit on the CPU  
Rack in two series unless an Expansion CPU Rack is connected, in which case  
only six Expansion I/O Racks may be connected. If an Expansion CPU Rack is  
connected, one of the series of Expansion I/O Racks is connected to the I/O  
Control Unit on the CPU Rack and the other one is connected to the I/O Interface  
Unit on the Expansion CPU Rack.  
Attach a Termination Resistance Unit to the unused terminal on the I/O Interface  
Unit of the last Expansion I/O Rack in each series. If two series of Expansion I/O  
Racks are used, connect a Termination Resistance Unit to the last Rack in each.  
I/O Connector Connects Expan-  
sion I/O Rack to preceding Expan  
sion I/O, Expansion CPU, or CPU  
Rack.  
-
Expansion I/O  
Backplane  
CV500-BI042/062/  
T
ermination Resistance Unit  
A Termination Resistance Unit  
must be connected to the unused  
I/O Connecting Cable Connector  
when an Expansion I/O Rack is  
not connected.  
112 or  
CVM1-BI064/114  
I/O Connector Connects Expan-  
sion I/O Rack to next Expansion  
I/O Rack. When not used, connect  
to a Termination Resistance Unit.  
Power Supply Unit  
CV500-PS221/PS211  
or CVM1-PA208  
Units  
(Up to 4/6/11 or the following  
Units: C500 I/O Units, C500  
Special I/O Units, SYSMAC  
BUS Masters)  
I/O Interface Unit (CV500-II201)  
Connects the Expansion I/O Rack to  
other Expansion Racks, the CPU Rack,  
and/or an Expansion I/O Rack.  
Single Expansion I/O Rack  
If only one Expansion I/O Rack is required and no Expansion CPU Rack is used,  
single Expansion I/O Rack can be connected directly to the CPU Rack without  
a
an I/O Control Unit or I/O Interface Unit. The Racks are connected directly via the  
connectors on the two Backplanes. Termination Resistance Units are also not  
required. In every other respect, the Expansion I/O Rack is identical to Expan  
-
sion I/O Racks in connected via I/O Control and I/O Interface Units.  
25  