System Configuration  
Section 2-1  
Configuration Limits  
The following two tables indicate limits on the system configuration. The first  
table indicates limits for the basic System. The second table indicates limits for  
Remote I/O Systems.  
Basic System  
Item  
CV500 or  
CVM1-CPU01-EV2  
CV1000 or  
CVM1-CPU11-EV2  
CV2000 or  
CVM1-CPU21-EV2  
Number of I/O points  
512 points (32 words) 1,024 points  
(64 words)  
2,048 points  
(128 words)  
Number of connectable Expansion CPU Racks  
Number of connectable Expansion I/O Racks  
Number of I/O slots on CPU Rack  
1
7 (6 if an Expansion CPU Rack is also used)  
3/5/10  
11  
Number of I/O slots on Expansion CPU Rack  
Number of I/O slots on Expansion I/O Rack  
4/6/11  
Remote I/O Systems  
Item  
SYSMAC BUS/2 (see note 2)  
SYSMAC BUS  
CV500 or  
CVM1-CPU01  
-EV2  
CV1000,  
CV2000,  
CVM1-CPU11  
CV500 or  
CVM1-CPU01  
-EV2  
CV1000,  
CV2000, or  
CVM1-CPU11  
-EV2  
CVM1-CPU21  
-EV2  
-EV2, or  
CVM1-CPU21  
-EV2  
Limits  
per PC  
No. of remote I/O  
points  
1,024 pts  
(64 words)  
2,048 pts  
(128 words)  
512 pts  
(32 words)  
1,024 pts (64  
words)  
2,048 pts (128  
words)  
No. of Remote  
Masters  
2
4
4
8
No. of Slave Racks ---  
---  
8
2
16  
8
Limits  
per  
Remote  
No. of Slaves (see  
note 1)  
58M Slaves: 8 Units  
122M Slaves: 4 Units  
54MH Slaves: 4 Units  
I/O  
Master  
Unit  
No. of remote I/O  
points  
58M Slaves: 464 input and 464  
output  
512 pts (32 words)  
122M Slaves: 976 input and 976  
output  
54MH Slaves: 432 input and  
432 output  
Combined No. of  
Slaves, I/O Link  
Units, Optical I/O  
Units, and I/O  
Terminals  
---  
64 (optical)  
32 (wired)  
Expansion I/O Backplanes  
CV500-BI112/062/042  
C500-BI081/051  
Note 1. 58M Slaves are counted as one Unit and 122M and 54 MH Slaves are  
counted as two Units in figuring the total of eight connectable Units. 58M,  
122M, and 54MH classifications are set with a switch on the Slave.  
2. A SYSMAC BUS/2 Slave must be designated “54MH” to use  
READ(190)/WRIT(191) for Special I/O Units mounted to it. These instruc-  
tions cannot be used for SYSMAC BUS Slaves regardless.  
22  