Power Supply Units  
Section 3-4  
Surge Current  
The surge current for the DC Power Supply Unit under maximum load conditions  
is shown below. Consider the surge current characteristics when selecting the  
power source, switches, breakers, etc.  
Electric  
current  
(A)  
Time (ms)  
Input: 24 VDC; load: 12 A at 5 V (maximum load); ambient temp.: 25°C.  
Use crimp terminals for wiring. Do not connect bare stranded wires directly to  
terminal blocks. Use M3.5 screws for tightening crimp terminals.  
7 mm max.  
7 mm max.  
Tighten the screws on the terminal block to a torque of 0.8 N S m.  
20 mm max.  
M3.5 screw  
Tightening torque: 0.8 N S m  
Caution Abide by the following precautions when wiring the Power Supply Units. Failure  
!
to abide by these precautions my cause faulty operation or damage to the Unit.  
Be sure that no wire clippings or other foreign materials enter the Units when  
wiring.  
Provide circuit breakers and other protective devices to protect the system  
again external short circuits.  
Check and recheck all wiring before supplying power to the system.  
After wiring the terminals check the terminal block to be sure it is firmly locked  
in place.  
3-4-2 Grounding  
The line ground (LG: ) terminal of the Power Supply Unit is a noise-filtered  
neutral terminal. Short the line ground terminal to the ground (GR: ) terminal to  
improve noise resistance.  
To avoid electrical shock, attach a grounded AWG 14 wire (cross-sectional area  
2
of 2 mm ) to the ground terminal. The ground resistance must be 100  
W or less  
and must be checked periodically to be sure that environmental conditions have  
not deteriorated ground capacity. Do not use a wire longer than 20 m.  