 浏览型号3G3EV-AB007M-CUE的Datasheet PDF文件第30页浏览型号3G3EV-AB007M-CUE的Datasheet PDF文件第31页浏览型号3G3EV-AB007M-CUE的Datasheet PDF文件第32页浏览型号3G3EV-AB007M-CUE的Datasheet PDF文件第33页浏览型号3G3EV-AB007M-CUE的Datasheet PDF文件第35页浏览型号3G3EV-AB007M-CUE的Datasheet PDF文件第36页浏览型号3G3EV-AB007M-CUE的Datasheet PDF文件第37页浏览型号3G3EV-AB007M-CUE的Datasheet PDF文件第38页  
Design  
Chapter 3  
The cable between the Inverter and the motor should be as short as possible.  
Steel box  
Metal pipe  
3G3EV  
Power supply  
Noise  
Filter  
Noise  
Filter  
D Cable Length between Inverter and Motor  
If the cable between the Inverter and the motor is long, the high-frequency leakage current will increase,  
causing the Inverter output current to increase as well. This may affect peripheral devices. To prevent  
this, adjust the carrier frequency (set in n37) as shown in the table below.  
Cable length between Inverter and motor  
Carrier frequency (n37)  
20 m max.  
100 m max.  
10 kHz max. (1, 2, 3, 4)  
5 kHz max. (1, 2)  
Note When the cable length between Inverter and motor exceeds 20 m, the system must be con-  
firmed for conformity to the EMC Directives.  
H Ground Wiring  
Always use a ground terminal with the following ground resistance.  
200-VAC Class:  
400-VAC Class:  
100 or less  
10 or less  
Also connect to the power supply neutral.  
Do not share the ground wire with other devices such as a welder or power tool.  
Always use a ground wire that complies with technical standards on electrical equipment. Route the  
ground wire so that the total length is as short as possible.  
3-18  