Specifications
Chapter 4
4-1 Specifications of Main Unit
H Ratings
Model 3G3EV-
A2001(M)- A2002(M)- A2004(M)- A2007(M)- A2015(M)-
CUE CUE CUE CUE CUE
Three
phase,
200 VAC
Power
supply
Rated voltage and Three-phase, 200 to 230 VAC, 50/60 Hz
frequency
Allowable voltage –15% to 10 %
fluctuation
Allowable
frequency
fluctuation
5%
Heating value (W)
Weight (kg)
11.9
0.5
18.8
0.6
33.2
0.9
51.7
71.6
1.3
1.5
1.5
Maximum applicable motor capacity
(kW)
0.1
0.2
0.4
0.75
Output
specifi-
cations
Rated output capacity (kVA) 0.3
0.6
1.5
1.1
3.0
1.9
5.0
2.7
7.0
Rated output current (A)
Rated output voltage
0.8
Three-phase, 200 to 230 VAC (Corresponds to the input
voltage)
Maximum output frequency
400 Hz (Parameter setting)
Self-cooling
Cooling method
Model 3G3EV-
AB001(M)- AB002(M)- AB004(M)- AB007(M)- AB015(M)
CUE
CUE
CUE
CUE
-CUE
Single
phase/
Three
phase,
200 VAC
Power
supply
Rated voltage and Single-phase/Three-phase, 200 to 240 VAC, 50/60 Hz
frequency
Allowable voltage –15% to 10 %
fluctuation
Allowable
frequency
fluctuation
5%
Heating value (W)
Weight (kg)
Maximum applicable motor capacity
(kW)
12.6
0.5
20.3
0.6
25.3
1.3
55.3
1.3
78.4
2.0
1.5
0.1
0.2
0.4
0.75
Output
specifi-
cations
Rated output capacity (kVA) 0.3
0.6
1.5
1.1
3.0
1.9
5.0
2.7
7.0
Rated output current (A)
Rated output voltage
0.8
Three-phase, 200 to 230 VAC (Corresponds to the input
voltage)
Maximum output frequency
400 Hz (Parameter setting)
Self-cooling
Cooling method
Note Model numbers with a suffix of “-CUE” indicate models approved by UL. (Approval has not been
obtained for models with a model number suffix of “-CE.”)
4-2