欢迎访问ic37.com |
会员登录 免费注册
发布采购

3G2A9-AL004-PE 参数 Datasheet PDF下载

3G2A9-AL004-PE图片预览
型号: 3G2A9-AL004-PE
PDF下载: 下载PDF文件 查看货源
内容描述: 可编程控制器 [Programmable Controllers]
分类和应用: 控制器
文件页数/大小: 182 页 / 1513 K
品牌: OMRON [ OMRON ELECTRONICS LLC ]
 浏览型号3G2A9-AL004-PE的Datasheet PDF文件第19页浏览型号3G2A9-AL004-PE的Datasheet PDF文件第20页浏览型号3G2A9-AL004-PE的Datasheet PDF文件第21页浏览型号3G2A9-AL004-PE的Datasheet PDF文件第22页浏览型号3G2A9-AL004-PE的Datasheet PDF文件第24页浏览型号3G2A9-AL004-PE的Datasheet PDF文件第25页浏览型号3G2A9-AL004-PE的Datasheet PDF文件第26页浏览型号3G2A9-AL004-PE的Datasheet PDF文件第27页  
Networks and Remote I/O Systems  
Section 1-6  
SYSMAC BUS Remote I/O  
System  
Remote I/O can also be enabled by using the C-series SYSMAC BUS Remote  
I/O System with CV-series PC.  
Remote I/O Master Units can be mounted on any slot of the CPU Rack, Expan  
-
sion CPU Rack, or Expansion I/O Rack. Up to four Masters can be mounted for  
the CV500 or CVM1-CPU01-EV2, up to eight Masters for the CV1000, CV2000,  
or CVM1-CPU11/21-EV2.  
For each Master, up to two Slave Racks can be connected for the CV500 or  
CVM1-CPU01-EV2; up to eight Slave Racks for the CV1000, CV2000, or  
CVM1-CPU11/21-EV2. No more than 16 Slave Racks can be connected per PC.  
Slaves can be used to provide up to 512 remote I/O points for the CV500 or  
CVM1-CPU01-EV2; up to 1,024 remote I/O points for the CV1000, CV2000, or  
CVM1-CPU11-EV2; up to 2,048 remote I/O points for the CVM1-CPU21-EV2.  
These limits are the totals for all Slaves control by one PC.  
Programming Devices cannot be connected to SYSMAC BUS Slave Racks.  
Remote I/O Master Unit  
3G2A5-RM001-(P)EV1 (optical)  
C500-RM201 (wired)  
CV500, CVM1-CPU01-EV2:  
2 Masters max. can be mounted  
CV1000, CV2000, CVM1-CPU11/21-EV2: 4 Masters max. can be mounted  
Up to 8 Units  
CV-series  
CPU Rack/Expansion CPU  
Rack/Expansion I/O Rack  
C-series  
Remote I/O Slave Rack  
Host Link System  
(SYSMAC WAY)  
The CV-series PCs can be connected to a host computer with the host link con  
nector via the CPU or a CV500-LK201 Host Link Unit mounted to a Rack.  
-
-
RS-232C or RS-422 communications can be used depending on the switch set  
ting. When RS-422 is selected, up to 32 PCs can be connected to a single host.  
Data is transmitted and received by commands and responses.  
Host  
computer  
Host link connector  
10  