 浏览型号CAR0812FPBX5Z01A的Datasheet PDF文件第4页浏览型号CAR0812FPBX5Z01A的Datasheet PDF文件第5页浏览型号CAR0812FPBX5Z01A的Datasheet PDF文件第6页浏览型号CAR0812FPBX5Z01A的Datasheet PDF文件第7页浏览型号CAR0812FPBX5Z01A的Datasheet PDF文件第9页浏览型号CAR0812FPBX5Z01A的Datasheet PDF文件第10页浏览型号CAR0812FPBX5Z01A的Datasheet PDF文件第11页浏览型号CAR0812FPBX5Z01A的Datasheet PDF文件第12页  
Data Sheet  
GE  
CAR0812FP series rectifier  
Input: 85VAC to 264VAC; Output: 12VDC @ 850W; 3.3VDC or 5 VDC @ 1A  
preceding read instructions. The PEC is appended to the  
message by the device that supplied the last byte.  
Digital Feature Descriptions  
PMBus™ compliance: The power supply is fully compliant  
to the Power Management Bus (PMBus™) rev1.2  
requirements.  
SMBAlert#: The µC driven SMBAlert# signal informs the  
‘master/host’ controller that either a STATE or ALARM  
change has occurred. Normally this signal is HI. The signal  
will change to its LO level if the power supply has changed  
states and the signal will be latched LO until the power  
supply either receives a ‘clear’ instruction as outlined below  
or executes a READ STATUS_WORD. If the alarm state is still  
present after the STATUS registers were reset, then the  
signal will revert back into its LO state again and will latch  
until a subsequent reset signal is received from the host  
controller.  
Manufacturer specific commands located between  
addresses 0xD0 to 0xEF provide instructions that either do  
not exist in the general PMBus specification or make the  
communication interface simpler and more efficient.  
Master/Slave: The ‘host controller’ is always the MASTER.  
Power supplies are always SLAVES. SLAVES cannot initiate  
communications or toggle the Clock. SLAVES also must  
respond expeditiously at the command of the MASTER as  
required by the clock pulses generated by the MASTER.  
The signal will be triggered for any state change, including  
the following conditions;  
Clock stretching: The ‘slave’ µController inside the power  
supply may initiate clock stretching if it is busy and it desires  
to delay the initiation of any further communications. During  
the clock stretch the ‘slave’ may keep the clock LO until it is  
ready to receive further instructions from the host controller.  
The maximum clock stretch interval is 25ms.  
VIN under or over voltage  
Vout under or over voltage  
IOUT over current  
Over Temperature warning or fault  
Fan Failure  
Communication error  
PEC error  
Invalid command  
The host controller needs to recognize this clock stretching,  
and refrain from issuing the next clock signal, until the clock  
line is released, or it needs to delay the next clock pulse  
beyond the clock stretch interval of the power supply.  
Internal faults  
Note that clock stretching can only be performed after  
completion of transmission of the 9th ACK bit, the exception  
being the START command.  
The power supply will clear the SMBusAlert# signal (release  
the signal to its HI state) upon the following events:  
Receiving a CLEAR_FAULTS command  
The main output recycled (turned OFF and then ON) via  
the ENABLE signal pin  
The main output recycled (turned OFF and then ON) by  
the OPERATION command  
Execution of a READ of the STATUS_WORD register  
Global broadcast: This is a powerful command because it  
can instruct all power supplies to respond simultaneously in  
one command. But it does have a serious disadvantage.  
Only a single power supply needs to pull down the ninth  
acknowledge bit. To be certain that each power supply  
responded to the global instruction, a READ instruction  
should be executed to each power supply to verify that the  
command properly executed. The GLOBAL BROADCAST  
command should only be executed for write instructions to  
slave devices.  
Clock  
Stretch  
Figure 1. Example waveforms showing clock  
stretching.  
I²C Bus Lock-Up detection: The device will abort any  
transaction and drop off the bus if it detects the bus being  
held low for more than 35ms.  
Communications speed: Both 100kHz and 400kHz clock  
rates are supported. The power supplies default to the  
100kHz clock rate. The minimum clock speed specified by  
SMBus is 10 kHz.  
Read back delay: The power supply issues the SMBAlert #  
notification as soon as the first state change occurred.  
During an event a number of different states can be  
transitioned to before the final event occurs. If a read back is  
implemented rapidly by the host a successive SMBAlert#  
could be triggered by the transitioning state of the power  
supply. In order to avoid the triggering of successive  
SMBAlert# s and thus reading a transitioning state, it is  
prudent to wait more than 2 seconds after the receipt of an  
SMBAlert# before executing a read back. This delay will  
ensure that only the final state of the power supply is  
captured.  
Packet Error Checking (PEC): Although the power supply will  
respond to commands with or without the trailing PEC, it is  
highly recommended that PEC be used in all  
communications. The integrity of communications is  
compromised if packet error correction is not employed.  
There are many functional features, including turning OFF  
the main output, that should require validation to ensure  
that the correct command is executed.  
Successive read backs: Successive read backs to the power  
supply should not be attempted at intervals faster than  
every one second. This time interval is sufficient for the  
PEC is a CRC-8 error-checking byte, based on the polynomial  
C(x) = x8 + x2 + x + 1, in compliance with PMBus™  
requirements. The calculation is based in all message bytes,  
including the originating write address and command bytes  
May 2, 2013  
©2013 General Electric Company. All rights reserved.  
Page 8  