Data Sheet
GE
CAR0812FP series rectifier
Input: 85VAC to 264VAC; Output: 12VDC @ 850W; 3.3VDC or 5 VDC @ 1A
Environmental Specifications
Parameter
Ambient Temperature
Min
-106
-40
Typ
Max
70
Units
°C
Notes
Derated above 50C
Storage Temperature
85
°C
Operating Altitude
2250/7382
8200/30k
2.5
m/ft
m / ft
%/°C
Non-operating Altitude
Power Derating with Temperature
Power Derating with Altitude
50C to 70C
2.0
Above 2250 m/7382 ft
C/301 m
C/1000 ft
Acoustic noise
55
dbA
°C
Full load
Over Temperature Protection
125/110
Shutdown / restart
Humidity
Operating
Storage
30
10
95
95
%
Relative humidity, non-condensing
Shock and Vibration acceleration
NEBS GR-63-CORE, Level 3, 20 -
2000Hz, min 30 minutes
6
Grms
Zone
Earthquake Rating
NEBS GR-63-CORE, all floors, Seismic
Zone 4 Designed and tested to meet
NEBS specifications.
4
EMC Compliance
Parameter
Criteria
Conducted emissions
Standard
Level
Test
EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2
A – Z01A 0.15 – 30MHz
B – Z01B 0 – 2 KHz
AC input7
Radiated emissions
Voltage dips
EN55022
A – Z01A 30 – 10000MHz
B – Z01B
EN61000-4-11
A
B
B
A
A
B
A
A
A
B
-30%, 10ms
-60%, 100ms
-100%, 5sec
AC Input immunity
Voltage surge
EN61000-4-5
2kV, 1.2/50µs, common mode
1kV, 1.2/50µs, differential mode
5/50ns, 2kV (common mode)
130dBµV, 0.15-80MHz, 80% AM
10V/m, 80-1000MHz, 80% AM
Fast transients
EN61000-4-4
EN61000-4-6
EN61000-4-3
ENV 50140
Conducted RF fields
Radiated RF fields
Enclosure immunity
ESD
EN61000-4-2
4kV contact, 8kV air
6
Designed to start at an ambient down to -40°C; meet spec after 30 min warm up period, may not meet operational limits below -10°C.
7 The ….Z01A module meets class A emissions, the …..Z01B module meets class B emissions (see ordering section)
May 2, 2013
©2013 General Electric Company. All rights reserved.