Function Diagram:
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
CLASS I, ZONE 0, GROUP IIC
Safety Description
Terminals 15-12
(with 16-11 shorted)
Uo/Voc = 2.2 V
Io/Isc = 38 mA
Po/Po = 21 mW
Group Co/Ca Lo/La
Lo/Ro
Cenelec (µF) (mH) (µH/Ω)
IIC
IIB
IIA
100
1000
1000
11.3
45.3
90.7
849
3396
6793
MODEL D1010D Duplicator
3 +
=
=
Supply 24 Vdc
Out 1-A
4 -
=
Source I
+
Source V
External
Powered Tx
14
1
2
8
+
-
Sink I
=
mA RL
15
16
+
+
-
V
RL
+
-
mA
In 1
=
-
=
=
Out 1-B
=
Source I
+
Source V
10
11
12
5
6
7
+
-
Sink I
=
mA RL
+
-
V
RL
+
-
mA
=
Connections for Duplication of Active Input Signals
Restriction on specifications for external powered Transmitter:
The voltage drop must be changed in 1.8 V maximum
The safety parameters must be changed in: Uo/Voc = 2.2 V, Io/Isc = 38 mA, Po/Po = 21 mW
G.M. International DTS0016-19 Page 4/4