Type XHHW-2 or RHH/RHW-2/USE-2
GenFree® II LSZH XLPO Single Conductor
Specifications 5075, 5125 & 5275
GenFree II LSZH XLPO Low-Voltage Power
Single and Dual Layer Cross-linked Polyolefin Single Conductor
Rated for 600 Volts or 2000 Volts (AC or DC)
For Use in all Closed Environments, Commercial / Utility / Industrial Applications, Free Air or Direct Burial
D. Smoke and Halogen Testing – Low-Smoke/Zero-Halogen:
Meets the requirements of the UL1685 Method 1 flame and smoke test,
as well as the halogen, smoke, and acid gas requirements of ICEA T-33-
655, allowing the cable to be listed and printed “ST1” to indicate
compliance with the UL44 standard.
GenFree II Smoke Generation and Halogen Content Test Requirements:
Type II Thermoset
Property or Test
ICEA T-33-655
Requirements
Physical Properties
Hot Creep After Conditioning @ 150ºC
Table I
Elongation
Set
100% max
10% max
50 mg/in2max
Gravimetric Water Absorption @ 75ºC
Table II
Acid Gas Equivalent
Per MIL-C-24643
Halogen Content
Table III
Table III
2% max
Per MIL-C-24643
0.2% max
Smoke Generation 80 mil Plaque
Flaming Mode Ds @ 4 minutes
Flaming Mode Dm
Table III
ASTM E662
50 max
250 max
50 max
Non-Flaming Mode Ds @ 4 minutes
Non-Flaming Mode Dm
350 max
6