Type XHHW-2 or RHH/RHW-2/USE-2
GenFree® II LSZH XLPO Single Conductor
Specifications 5075, 5125 & 5275
GenFree II LSZH XLPO Low-Voltage Power
Single and Dual Layer Cross-linked Polyolefin Single Conductor
Rated for 600 Volts or 2000 Volts (AC or DC)
For Use in all Closed Environments, Commercial / Utility / Industrial Applications, Free Air or Direct Burial
GenFree II Physical Properties Test Requirements:
Property or Test
UL 44
Requirements
Unaged
Table 11
Tensile Strength (psi)
Elongation (%)
1500 min
150 min
Aged
Table 11
Tensile Retention (% of original)
Elongation Retention (% of original)
70
70
Property or Test
UL 854 USE-2
Requirements
Physical Properties
Impact Resistance Test
5 lbs., 1 ft. drop
Crushing Resistance Test
Test without current
Test with rated current
Test with overload current
Para. 23
Para. 24
8 of 10 no current leak
1000 lbf min
800 lbf min
600 lbf min
B. Electrical properties:
Meets or exceeds all requirements of UL 44 Type XHHW-2, RHH, RHW-2, UL 854 Type
SE-2, and ICEA S-95-658/NEMA WC70 for operation at 90°C for both wet and dry
environments.
Property or Test
UL 44
Requirements
Physical Properties
Insulation Resistance in Water @ 90ºC
Insulation Resistance
Rate of Decrease >10 MΩ/kft
Capacitance and Relative Permittivity @ 90ºC
Relative Permittivity
Para. 5.4
0.180 MΩ/kft min
4% decrease max
6.0 max
Increase in Capacitance
1-14 Day
7-14 Day
10.0% max
4.0% max
Para. 5.6
4