欢迎访问ic37.com |
会员登录 免费注册
发布采购

GWACCZ 参数 Datasheet PDF下载

GWACCZ图片预览
型号: GWACCZ
PDF下载: 下载PDF文件 查看货源
内容描述: 划音频指挥中心语音疏散控制面板 [Zoned Audio Command Center Voice Evacuation Control Panel]
分类和应用:
文件页数/大小: 4 页 / 164 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
 浏览型号GWACCZ的Datasheet PDF文件第1页浏览型号GWACCZ的Datasheet PDF文件第2页浏览型号GWACCZ的Datasheet PDF文件第4页  
Application Example: 50-watt zone splitting, eight speaker circuits  
50 watts total power with automatic control via ACS link from the FACP — see diagram below.  
This application of the GWACCZ configures the zone splitter module (ACC-ZSM) to divide 50 watts of audio from two audio  
amplifiers (ACC-AAM25) into four speaker circuits each. The FACP uses the ACS link connected to the zone page module  
with keypad (ACC-ZPMK) for automatic activation of the speaker zones and for alarm activation.  
Configuration switches are set as follows:  
• ACC-ZSM SW1 set to “AAM1 & AAM2” and SW2 to “Class B” to place speaker circuits 1 – 4 on AAM1  
and speaker circuits 5 – 8 on AAM2, configured for Style Y (Class B) wiring.  
• ACC-ZPMK DIP switch S1 set for communication with software version 2.x (1 = ON, 2 = OFF, 3 = OFF).  
• GWACCZ main circuit board DIP switch S3 set for single zone mode, All-Call and two messages  
(1 = ON, 2 = OFF, 3 = OFF).  
The FACP can automatically activate the Fire Evacuation Message and any combination of the eight speaker zones. For  
speaker circuit manual deactivation, press the activated zone pushbutton on the ACC-ZPMK keypad. For manual activa-  
tion, press either of the Message push-buttons, then select the Zone pushbutton on the ACC-ZPMK keypad. For All-Call  
Paging, press the All-Call pushbutton on the main panel keypad, then key the microphone to make an announcement.  
GWACCZ CS-2505 09/01/06  
Page 3 of 4  
 复制成功!