 浏览型号BMR4560004/018的Datasheet PDF文件第31页浏览型号BMR4560004/018的Datasheet PDF文件第32页浏览型号BMR4560004/018的Datasheet PDF文件第33页浏览型号BMR4560004/018的Datasheet PDF文件第34页浏览型号BMR4560004/018的Datasheet PDF文件第36页浏览型号BMR4560004/018的Datasheet PDF文件第37页浏览型号BMR4560004/018的Datasheet PDF文件第38页浏览型号BMR4560004/018的Datasheet PDF文件第39页  
E
35  
Technical Specification  
BMR456 series Fully regulated Advanced Bus Converters  
1/28701-FGC 101 1823 revD February 2013  
© Ericsson AB  
Input 36-75 V, Output up to 39 A / 468 W  
also reduce any high frequency noise at the load. It is equally  
important to use low resistance and low inductance PWB  
layouts and cabling. External decoupling capacitors will  
become part of the product’s control loop. The control loop is  
optimized for a wide range of external capacitance and the  
maximum recommended value that could be used without any  
additional analysis is found in the electrical specification.  
The ESR of the capacitors is a very important parameter.  
Stable operation is guaranteed with a verified ESR value of  
>10 macross the output connections.  
Please contact your local Ericsson Power Modules  
representative for appropriate SW tools to down-load new  
configurations.  
Output Voltage Adjust using PMBus  
The output voltage of the product can be reconfigured using  
the PMBus interface.  
Margin Up/Down Controls  
These controls allow the output voltage to be momentarily  
adjusted, either up or down, by a nominal 10%. This provides  
a convenient method for dynamically testing the operation of  
the load circuit over its supply margin or range. It can also be  
used to verify the function of supply voltage supervisors.  
The margin up and down levels of the product can be re-  
configured using the PMBus interface.  
For further information please contact your local Ericsson  
Power Modules representative.  
Parallel Operation (Droop Load Share, DLS)  
The BMR456, DLS products, (product-number ending /013,  
/014, /016 or /017) are variants that can be connected in  
parallel. The products have a pre-configured voltage droop:  
The stated output voltage set point is at no load. The output  
voltage will decrease when the load current is increased. The  
voltage will droop 0.6 V while load reaches max load. This  
feature allows the products to be connected in parallel and  
share the current with 10% accuracy. Up to 90% of max  
output current can be used from each product.  
Soft-start Power Up  
The default rise time of the ramp up is 10 ms. When starting  
by applying input voltage the control circuit boot-up time adds  
an additional 15 ms delay. The soft-start power up of the  
product can be reconfigured using the PMBus interface.  
The DLS variants have a pre-configured ramp up time of  
25 ms.  
When running DLS-products in parallel command (0xF9) must  
be set according to MFR_MULTI_PIN_CONFIG. To prevent  
unnecessary current stress, changes of the output voltage  
must be done with the output disabled. This must be  
Remote Sense  
The product has remote sense that can be used to  
compensate for voltage drops between the output and the  
point of load. The sense traces should be located close to the  
PWB ground layer to reduce noise susceptibility. The remote  
sense circuitry will compensate for up to 10% voltage drop  
between output pins and the point of load. If the remote sense  
is not needed +Sense should be connected to +Out and  
-Sense should be connected to -Out. To be able to use remote  
sense the converter must be equipped with a Communication  
interface.  
considered for all commands that affect the output voltage.  
Voltage regulation DLS products  
12.8  
Module 1  
Module 2  
12.6  
Module 1+2  
12.4  
12.2  
12.0  
11.8  
11.6  
Temperature Protection (OTP, UTP)  
The products are protected from thermal overload by an  
internal temperature shutdown protection.  
When TP1 as defined in thermal consideration section is  
exceeded the product will shut down. The product will make  
continuous attempts to start up (non-latching mode) and  
resume normal operation automatically when the temperature  
has dropped below the temperature threshold set in the  
command OT_WARN_LIMIT (0x51); the hysteresis is defined  
in general electrical specification.  
The OTP and hysteresis of the product can be re-configured  
using the PMBus interface. The product has also an under  
temperature protection. The OTP and UTP fault limit and fault  
response can be configured via the PMBus. Note: using the  
fault response “continue without interruption” may cause  
permanent damage to the product  
0
10  
20  
30  
40  
50  
60  
70  
Output Current [A]  
Feed Forward Capability  
The BMR456 products have a feed forward function  
implemented that can handle sudden input voltage changes.  
The output voltage will be regulated during an input transient  
and will typically stay within 10% when an input transient is  
applied.  
PMBus configuration and support  
Over Voltage Protection (OVP)  
The product provides a PMBus digital interface that enables  
the user to configure many aspects of the device operation as  
well as monitor the input and output parameters.  
The product includes over voltage limiting circuitry for  
protection of the load. The default OVP limit is 30% above the  
nominal output voltage. If the output voltage exceeds the OVP  