NH DIN Dual Indication Fuse Links
Class gG/gL, 690Vac, 6 to 100 Amps, Size 0
Size 0 Time-Current Characteristics
NH
(Amps)
Size 0 Technical Data
I
2
t (Amps
2
Seconds)
Part Numbers with
Metal Gripping Lugs
6NHG0B-690
10NHG0B-690
16NHG0B-690
20NHG0B-690
25NHG0B-690
32NHG0B-690
35NHG0B-690
40NHG0B-690
50NHG0B-690
63NHG0B-690
80NHG0B-690
100NHG0B-690
Amp
Rating
6
10
16
20
25
32
35
40
50
63
80
100
Minimum
Pre-arcing
14
58
240
490
1200
1800
2400
3300
3000
5500
9800
18000
*I1 120kA
@ 690Vac
25
430
1400
2800
5400
10800
12700
16500
14700
26000
44000
75000
Watts
Loss
2
2
3
3.5
3.2
4.8
4.7
5
6
7
8.5
9.5
0.245kg
Net Weight
per Fuse
* I1 is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
Dimensions - mm
28-01-2010
BU-SB10048
Form No.NH690V
Page 3 of 7
Data Sheet 720109