NH DIN Dual Indication Fuse Links
Class gG/gL, 690Vac, 2 to 125 Amps, Size 000 & 00
Size 000 & 00 Time-Current Characteristics
NH
(Amps)
Size 000 & 00 Technical Data
I
2
t (Amps
2
Seconds)
Part Numbers with
Metal Gripping Lugs
2NHG000B-690
4NHG000B-690
6NHG000B-690
10NHG000B-690
16NHG000B-690
20NHG000B-690
25NHG000B-690
32NHG000B-690
35NHG000B-690
40NHG000B-690
50NHG00B-690
63NHG00B-690
80NHG00B-690
100NHG00B-690
125NHG00B-690
Amp Rating
Minimum
Pre-arcing
3.5
6
14
60
240
500
920
1800
2400
3300
3000
5500
9800
18000
36000
*I1 120kA
@ 690Vac
8
16
25
400
1200
2500
4400
9600
12700
15000
21000
38000
67000
119000
210000
Watts
Loss
4
2
2
1.5
2.5
2.5
3.5
3.5
4
4
5
6
7
9.5
10.5
0.200kg
0.133kg
Net Weight
per Fuse
2
4
6
10
16
20
25
32
35
40
50
63
80
100
125
* I1 is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
Dimensions - mm
Size 000
Size 00
28-01-2010
BU-SB10048
Form No.NH690V
Page 2 of 7
Data Sheet 720109