TM  
Prelim. Specification  
HBO80A-48-2.5  
BTCPower  
48Vin 2.5Vout 80A  
Protection Features  
Over Temperature Protection ( OTP )  
Input Under-voltage lockout ( IUV )  
The unit will shut down when the base plate  
temperature exceeds the protection threshold.  
Input under voltage ( IUV ) is standard with the  
HBO / HBP unit. The unit will shut down when the  
input voltage drops below a threshold, and the  
unit will turn on when the input voltage goes to  
the upper threshold.  
The unit will shut down under the base plate  
temperature over a 105°C condition to protect the  
unit from overheating. The OTP circuit will turn  
the unit off when OTP happens. Once the unit  
has shut down, it will restart at the cycle when the  
base plate temperature goes down.  
The hysteretic voltage of the under voltage  
protection is 1V, normally from the 34.5V to 35.4V  
range.  
Output Over-current Protection ( OCP )  
The unit will shut down when the over current or  
short circuit condition exists.  
Once the OCP happens, the unit has shut down.  
The attempted restart will continue indefinitely  
until the over current or short circuit condition is  
removed. When OCP happens, the output  
voltage drops below 0.8V.  
Input voltage has almost no effect on the current  
limit point.  
Output Over-voltage Protection ( OVP )  
The unit will shut down when the output voltage  
exceeds the over voltage threshold.  
If the output voltage across Vout(+) (pin9) and  
Vout(-) (pin5) exceeds the threshold of the OVP  
circuitry, the unit has shut down which is caused  
by an OVP circuit, and the unit will never restart,  
and the output voltage is below 0.5V.  
Broadband TelCom Power, Inc. 1719 S. Grand Avenue, Santa Ana, CA 92705 U.S.A.  
P 7 of 8  
Tel.: 714-259-4888 • Fax: 714-259-0840 • www.btcpower.com • Email: sales@btcpower.com • PS HBO80A-48-2.5 Rev1.2 12-8-03  