Description of Output Options
Option - PMU for
analog output
U1, U2, U8 and I1
Programming of the start and end value by the customer:
The option PMU allows to program the start value and the end value of the output range
by a programming signal SPAN/ZERO available at the connector. This Signal SPAN/ZERO
must be connected with GND via a push button, then position magnet of the sensor must
be moved to the start resp. end position. Pushing the button between 2 and 4 seconds sets
the actual position as start position, pushing the button more than 5 seconds sets the actual
position as end position. The values will be stored and are available after switching off the
sensor.
To reset the sensor to the factory values the button must be pushed for longer than two
seconds when the sensor is switched on.
Diagnostic on analog
outputs
Behaviour of the analog signal output in case of error
In case of error (magnet missing or outside the measuring range) the analog output signal
will assume a state according to the following options:
Alarm_HIGH
The output voltage resp. the output current is at HIGH level (overrange).
Alarm_LOW
The output voltage resp. the output current is at LOW level (underrange).
Alarm_HOLD
The output voltage resp. the output current will keep the last valid state.
Alarm_HIGH
Alarm_LOW
Alarm_HOLD
(standard)
(.../U)
(.../H)
keeps last valid state
(Order code U1/H)
Uout ≥ 10,5 V
Uout ≥ 10,5 V
Uout ≥ 10 V
—
U1
U2
U8
I1
Uout < 0,25 V
(Order code U2/U)
keeps last valid state
(Order code U2/H)
Uout < 0,25 V
(Order code U8/U)
keeps last valid state
(Order code U8/H)
1,5 ... 2 mA
(Order code I1/U)
keeps last valid state
Iout ≥ 21 mA
(Order code I1/H)
Error signal for
SSI output
If the sensor cannot detect a magnet the position value will assume the maximum value
(0xFFFFFFF).