9
■ Setting Specifications
[Setting contents]
[Data output item]
Instantaneous values
:
:
1P2W, 1P3W, 3P3W2M, 3P3W3M, 3P4W, 3P4W4I
9694, 9660, 9661, 9667, 9669, 9695-02 and 9695-03 (* A
different sensor can be set for each system.)
:
:
Voltage, current, active power, reactive power, apparent power,
power factor, frequency, average voltage, average current, (average
values are for each system)
Measurement line settings
Clamp-on sensor settings
:
:
:
:
0.01 to 9999.99 (* A different CT ratio can be set for each system.)
Manual or time (year, month, day, hour, minute)
Manual, time, or timer (1 seconds to 8784 hours)
Standard or fast (*Maximum measurement period: 1 year)
Standard interval: 1, 2, 5, 10, 15, or 30 seconds, or 1, 2, 5, 10, 15, 30,
or 60 minutes
* The instantaneous value for interval output.
VT (PT) and CT ratio settings
Measurement start method
Measurement stop method
Output Interval
Voltage, current, active power, reactive power, apparent power,
power factor, frequency, average voltage, average current, (average
values are for each system)
Average value
* The average value for each interval.
:
:
Voltage, current, active power, reactive power, apparent power,
power factor, frequency
Maximum/minimum value
Integrated value
Fast interval:
A single waveform, or 0.1, 0.2, or 0.5 seconds
:
:
PC card, internal memory, or printer
Automatically attached, or set the desired name
(up to 8 alphanumeric characters)
* The maximum/minimum value for each interval (no event details provided).
Data output destination
File name
Active power (consumption/regeneration)
Reactive power (lag/lead)
:
:
:
OFF, 2, 5, 10, 20 times (for movement averaging)
PC card, internal memory, or printer
Japanese, English, German, French, Italian, Chinese (Simple, Trad),
Spanish , Korean
Reactive power measurement method selection, harmonic distortion
selection, order display selection, backlight settings, ID settings,
clock settings, etc.
* The total value since the beginning of time series measurement, and the power volume for each interval.
Active power (consumption), reactive power (lag), power factor
* The value for each interval.
Display averaging circuit
Screen copy destination
Display language settings
:
:
:
:
:
Demand value
Maximum demand value
Harmonic
The maximum demand value since the beginning of time series
measurement and the time and date it occurred.
:
Other settings
Each harmonic order (level, content percentage, and phase angle),
total value, instantaneous value for THD-F/THD-R
Each harmonic order (level, content percentage, and phase angle),
total value, average value for THD-F/THD-R for each interval
Each harmonic order (level, content percentage, and phase angle),
total value, maximum/minimum value for THD-F/THD-R within
[File operations]
Copy file
Load/Save selected file
Delete file
Format
Storage format
:
:
:
:
:
Copies files from the internal memory to the PC card.
Loads/Saves the file(s) selected from the internal memory or PC card.
Deletes the file(s) from the PC card.
each interval
(no event data provided)
Initializes the PC card or internal memory.
:
:
Waveform (Voltage or current)
Exceeds the voltage/current crest factor, PLL unlock, power failure,
exceeds the display limit
Waveform
Status information
Measurement data:
CSV format
(binary format when using the fast interval setting)
Waveform data:
Screen data:
Settings data:
Binary format
BMP format
CSV format
[Print items]
Numerical values
:
:
Prints the data selected as the data output item (during time series
measurement).
Hard copy of the screen (printing of each interval not available)
Waveform
■ External Interface Specifications
■ Formulae
(for single-phase 2-wire systems)
[D/A output]
U : Inter-line voltage
I : Line current
(3169-21 only)
Number of output channels
Output items
:
:
4 channels
For instantaneous values: Voltage, current, average voltage, average current,
Active power, reactive power, apparent power,
power factor, frequency
M: Number of samples
s : Sample count
For Integrated value:
Active power (consumption/regeneration) or
reactive power (lag/lead)
m : 128 samples per cycle
For harmonics:
Each harmonic order (level, content percentage,
and phase angle), total value, THD-F/THD-R
:
:
:
:
:
:
±5V DC/f.s.
Polarity + 11 bits
Measurement accuracy ±0.2% f.s.
Less than ±0.02% f.s./°C
Output level
Resolution
● Measurement is also possible using the reactive
Output accuracy
Temperature characteristic
Output resistance
Output update rate
power measurement method
In addition to conventional calculation methods that search for reactive power
using voltage, current, and active power, you can select the reactive power
measurement method, which derives reactive power directly from voltage and
current values, just as with the reactive power volume measurement method
used in large-volume power consumers.
100Ω ±5%
For each cycle of measurement input (when a measurement item other than harmonics is set)
For every 16 cycles of measurement input (when harmonics is set as the measurement item)
[PC card]
:
:
Slot:
Card type:
1 × PC Card Standard-compliant Type II
Flash ATA card
When using the reactive power measurement method:
Compatible memory capacity: Up to 528 MB
Storage content:
Settings data, measurement data, screen data
Derives reactive power directly from
voltage and current values, just as with
the measurement of active power.
(The same measurement principle is
the same as that used to determine
reactive power by large-volume power
consumers.)
[RS-232C]
Printer or PC connected to an RS-232C interface
Compliance:
Transfer method:
EIA RS-232C-compliant
Asynchronous communication method,
full duplex
Baud rate:
2400, 9600, 19200, 38400 bps
Flow control and delimiter settings possible
[External I/O]
When not using the reactive power measurement method:
:
:
:
Start/stop control for time series measurement, data storage
LOW level is output during time series measurement.
A 0/5 V logic signal or a short-circuit/release contact signal
Control input
Control output
Control signal level
Calculates reactive power after
calculating the apparent power using
the voltage, current, and RMS values.
■ General Specifications
:
:
:
Safety
EN61010
:
Indoors, up to 2000m(78.74ft) ASL
Conforming standards
Operating environment
Operating temperature
and humidity
Storage temperature
and humidity
Withstand voltage
(50/60 Hz for 15 sec.)
:
0 to 40˚C, 80% RH or less (non-condensating)
Pollution degree 2,
measurement category (anticipated transient overvoltage 6000V)
EMC
EN61326 Class A
EN61000 - 3 - 2, EN61000 - 3 - 3
:
:
-10 to 50˚C, 80% RH or less (non-condensating)
5.55 kVrms AC: Between the voltage input terminal and the 3169
casing
3.32 kVrms AC: Between the voltage input terminal and the
current input terminal/external interface terminal
2.3 kVrms AC: Between the power supply and the 3169 casing
1.39 kVrms AC: Between the power supply and the current input
terminal/external interface terminal
voltage cord set 9438-03 (1) (1 cord each of black, red, yellow,
and blue), voltage cord (1), input cord label (1), operating manuals
(2) (Advanced edition and Quick Start Guide), CD-R (1) (Advanced
edition , RS-232C interface operating manuals and CSV conversion
Software), connection cable 9441 (1) (for the 3169-21 only)
Accessories
:
:
:
100 to 240 V AC, 50/60 Hz
30 VA
Approx.210(8.27ʺ)W × 160(6.30ʺ) H × 60D(2.36ʺ) mm (excluding
protrusions),
Power supply voltage rating
Maximum rated power
Dimensions and weight
Approx.1.2 kg(42.3oz.) (3169-20, 3169-21)