DS1600SPE Data Sheet
Electrical Specifications
LED Indicators
A single bi-color LED is used to indicate the power supply status.
Status LED
Off
No AC input to PSU
Main output ON
Solid GREEN
Blinking AMBER
Standby mode and Power supply failure (OCP, OVP, OTP, FAN FAULT)
Firmware Reporting And Monitoring
Accuracy Range
20% to 50%
5%
Output loading
Input voltage
Input current
Input power
Output voltage
Output current
Temperature
EIN
8 to 20%
50% to 100%
0.55A
5%
5W at <125 W input power
1.25%
2%
1.2 A fixed error
3%
5 degC on the operating range
250 RPM
15% from 10% to 20% load
5%
Fan speed
PMBus
YES
YES
Remote ON/OFF