Technical Reference Note
Rev.07.04.14_#1.0
AVO100-36S3V3B-6L
Page 3
Electrical Specifications
Absolute Maximum Ratings
Stress in excess of those listed in the “Absolute Maximum Ratings” may cause permanent damage to the power supply.
These are stress ratings only and functional operation of the unit is not implied at these or any other conditions above
those given in the operational sections of this TRN. Exposure to any absolute maximum rated condition for extended
periods may adversely affect the power supply’s reliability.
Table 1. Absolute Maximum Ratings:
Parameter
Model
Symbol
Min
Typ
Max
Unit
Input Voltage
Operating -Continuous
Non-operating -100mS
All
All
-
-
-
-
80
100
Vdc
Vdc
VIN,DC
PO,max
Maximum Output Power
Isolation Voltage1
All
-
-
100
W
Input to outputs
input to metal
output to metal
-
-
-
-
-
-
1500
1000
1000
Baseplate module
Vdc
Ambient Operating Temperature
Storage Temperature
All
All
All
TA
-40
-55
-0.7
-
-
-
+85
+125
12
OC
OC
TSTG
Voltage at remote ON/OFF pin
Note 1 - 1mA for 60s, slew rate of 1500V/10s.
Vdc
Artesyn Embedded Technologies