64mm (2.52 in.)
58mm (2.28 in.)
8mm
13.5mm
13.5mm
13.5mm
5.8mm
(0.23 in.)
10.9mm
(0.43 in.)
22.9mm
(0.90 in.)
(0.31 in.) (0.53 in.) (0.53 in.) (0.53 in.)
1
N
1
3
5
N
46°
2
N
2
4
6
N
6.5mm
(0.26 in.)
3.2mm
15.7mm
(0.13 in.) (0.62 in.)
31mm (1.22 in.)
9mm
18mm
9mm
18mm
18mm
(0.71 in.)
18mm
(0.71 in.)
(0.35 in.) (0.71 in.)
(0.35 in.) (0.71 in.)
44mm (1.73 in.)
72mm (2.83 in.)
36mm (1.42 in.)
68mm (2.68 in.)
FI 2
FI 4
FI 2 and FI 4
Temperature Range
Environmental Information marked with “Snowflake” approval for -25°C to 40°C (-13°F to 104°F) ambient
temperature. (Temperature effect on RC: for every 10°C temperature rise above 40°C decrease RC by 7%.)
Fluctuating Climate Conditions
Electrical Shock Protection
To maximum 45°C, 95% relative humidity.
Uninsulated electrically live parts within 30mm of the operating handle are “finger safe” (terminal screw
heads) and uninsulated live parts within 100mm of the operating handle are “back-of-hand safe” (terminals).
15g with impact force half-cycle sinusoidal and 11ms duration, 18 impacts total with 6 on each principal axis
(3 impacts each face). FI is DIN Rail mounted during the test, and electrically loaded with 25% of Fault RC.
Successful testing required no trip during the test, no damage and no loosened parts.
Impact/Shock Protection
5g, at frequency of 55Hz to 2,000Hz, applied for 35 ± 5 minutes along each of the three principal axes, plus
5 minutes of application at every established critical resonant frequency. FI is DIN Rail mounted during the
test, and loaded with 25% Fault RC. To pass, the FI did not trip at 25% Fault RC, but did trip between each
of the principal axis tests when the fault current was raised to 125% Fault RC, and there was no damage
and no loosened parts. Suitable for machinery and mobile vehicle applications.
Vibration/Seismic Resistance
Ingress Protection (IP) Class 40; internal working components and live parts (excluding terminals) are
protected against ingress of solid objects greater than 1mm diameter (class 4-), but have no protection from
ingress of water (class-0).
Housing Class
The FI is tested and approval stamped for tripping sensitivity to non-sinusoidal fault currents, which become
zero or almost zero within one cycle of the line frequency. Waveforms and allowed trip-current ranges are as
follows:
Non-Sinusoidal Fault
1.
AC Sinusoidal Fault - 0.5-1.0 times Fault RC
2a.
2b.
Pulsating DC Fault;
Positive and Negative Half-Waves - 0.35-1.4 times Fault RC
Phased Half-Wave, 90° - 0.25-1.4 times Fault RC
Phased Half-Wave, 135° - 0.11-1.4 times Fault RC
3.
Pulsating DC on 6mA
DC (continuous) Base - Max. 1.4 times Fault RC + 6mA
At VDE rated voltage, suitable for Class C environments with relatively high dust and moisture levels and
little HVAC control, e.g., industrial, commercial, agricultural; on machine tools, hoists, warehouse equipment,
etc.; in boiler rooms, unheated storage, covered shipping/receiving, open workshops, etc.
Insulation Category