FI EARTH LEAKAGE
CIRCUIT BREAKERS
FI compact Earth Leakage Circuit
Breakers detect and interrupt earth
(ground) faults. They are VDE
approved for the European system
of protecting people, animals,
equipment and property from
dangerous line-to-ground and shock
hazard currents.
US applications include ground-fault
protection of equipment (GFPE)
using the 10mA and 30mA fault
current ratings, especially when high
distributed capacitance or other
leakages cause excessive nuisance
trips at lower fault currents.
Applications for the 300mA rating are
equipment protection and fire
prevention, limiting the energy of a
fault to less than the minimum
ignition energy for many materials.
a
FI 2
FI 4
Maximum
Rated
Line
Fault
Trip
Fault
Trip
Current
Current
Current
Type
Cat. No.
Type
Cat. No.
16A
10mA
FI 21.01 15.921
25A
25A
30mA
FI 22.03 15.922
FI 22.30 15.924
30mA
300mA
FI 42.03
FI 42.30
15.926
15.929
300mA
40A
40A
30mA
FI 23.03 15.923
FI 23.30 15.925
30mA
300mA
FI 43.03
FI 43.30
15.927
15.930
300mA
Type Designation
63A
63A
30mA
300mA
FI 44.03
FI 44.30
15.928
15.931
__
__
__
(c)
•
FI
(a) (b)
(a) = 2-2 pole; 4-4 pole
(b) = 1-16A; 2-25A; 3-40A; 4-63A
(c) = 01 - 10mA
Earth Leakage Circuit Breaker
Earth Leakage Circuit Breaker
with Auxiliary Contactsb
with Auxiliary Contactsb
25A
40A
63A
30mA
30mA
FI 22.03Y 15.932
FI 23.03Y 15.934
30mA
30mA
30mA
FI 42.03Y
FI 43.03Y
FI 44.03Y
15.933
15.935
15.936
= 03 - 30mA
= 30 - 300mA
Voltage Rating (maximum)
Short Circuit Capacity
240VAC, 50/60Hz
(VDE: 125/220VAC, 50Hz)
415VAC, 50/60Hz (400Hz available on request)
(VDE: 220/380VAC, 50Hz)
Up to rated current (RC) 40A = 1.5kA, RC 63A = 2kA. 10kA in combination with series fuse of
European Operation Class gL/gG: RC 16A = 63A fuse, RC 20/40A = 80A fuse, RC 63A = 100A fuse.
Fault Trip Current Calibration
FI trips are calibrated at less than fault trip current for ensured safety (Typical trip range between
66.6-83.3% fault trip current, e.g., typical trip at 20-25mA for fault RC of 30mA)
Typical Life
Fully functional after 4,000 operations to DIN/VDE 0664 (CEE27) and 16000 additional fault current trips.
Standard Pack and Weight
1/290g (0.64 lb.);
1/450g (1.0 lb.)
1/390g (0.86 lb.) with auxiliary contact
1/550g (1.21 lb.) with auxiliary contact
Terminal Size Acceptability
Equivalent Circuit
16-6 AWG
14-3 AWG
1
N
1 3 5 N
2
N
Test
2 4 6 N Test
a
For 2-Phase applications, terminal 5 and 6 (next
to Neutral terminals) must be connected to one
phase for the test circuit to be operable.
Note: If the power system has a marked conductor, it must connect through the FI and not be grounded at any
point downstream.
b
Provided with mounted Auxiliary Switch, one N.O.,
one N.C. isolated feedthrough contact (Form X
double make and Y double break), which adds
9mm (.35 in.) to the width dimension.