欢迎访问ic37.com |
会员登录 免费注册
发布采购

ADE7761ARS-REF 参数 Datasheet PDF下载

ADE7761ARS-REF图片预览
型号: ADE7761ARS-REF
PDF下载: 下载PDF文件 查看货源
内容描述: 电能计量IC ,带有片上故障和中性丢失检测 [Energy Metering IC with On-Chip Fault and Missing Neutral Detection]
分类和应用: 模拟IC信号电路光电二极管
文件页数/大小: 28 页 / 321 K
品牌: ADI [ ADI ]
 浏览型号ADE7761ARS-REF的Datasheet PDF文件第20页浏览型号ADE7761ARS-REF的Datasheet PDF文件第21页浏览型号ADE7761ARS-REF的Datasheet PDF文件第22页浏览型号ADE7761ARS-REF的Datasheet PDF文件第23页浏览型号ADE7761ARS-REF的Datasheet PDF文件第25页浏览型号ADE7761ARS-REF的Datasheet PDF文件第26页浏览型号ADE7761ARS-REF的Datasheet PDF文件第27页浏览型号ADE7761ARS-REF的Datasheet PDF文件第28页  
ADE7761  
Table 9. F1 and F2 Frequency with Half-Scale AC Inputs  
No-Load Threshold  
Frequency on F1 and F2,  
Ch 1 and Ch 2,  
Half-Scale AC Inputs (Hz)  
The ADE7761 includes a no-load threshold and startup current  
feature that eliminates creep effects in the meter. The ADE7761  
is designed to issue a minimum output frequency. Any load  
generating a frequency lower than this minimum frequency  
does not cause a pulse to be issued on F1, F2, or CF. The mini-  
mum output frequency is given as 0.0045% of the full-scale  
output frequency. (See Table 7 for maximum output frequencies  
for ac signals).  
S0  
0
0
1
1
S1  
0
1
0
1
F1–4  
1.72  
3.44  
6.86  
13.5  
0.085  
0.17  
0.34  
0.68  
When selecting a suitable F1–4 frequency for a meter design, the  
frequency output at IMAX (maximum load) with a meter constant  
of 100 impulses/kWh should be compared with Column 4 of  
Table 9. The frequency that is closest in Table 9 determines the  
best choice of frequency (F1-4). For example, if a meter with a  
maximum current of 40 A is being designed, the output  
frequency on F1 and F2 with a meter constant of  
For example, an energy meter with a meter constant of  
100 impulses/kWh on F1, F2 using SCF = 1, S1 = 0, and S0 = 1,  
the maximum output frequency at F1 or F2 is 0.68 Hz and 43.52  
Hz on CF. The minimum output frequency at F1 or F2 is  
0.0045% of 0.68 Hz or 3.06 × 10–5 Hz. This is 1.96 × 10–3 Hz at  
CF (64 × F1 Hz).  
100 impulses/kWh is 0.266 Hz at 40 A and 240 V (from  
Table 8). Looking at Table 9, the closest frequency to 0.266 Hz  
in Column 4 is 0.17 Hz. Therefore, F2 (3.4 Hz; see Table 5) is  
selected for this design.  
In this example, the no-load threshold is equivalent to 1.1 W of  
load or a startup current of 4.6 mA at 240 V. Compare this value  
to the IEC61036 specification, which states that the meter must  
start up with a load equal to or less than 0.4% IB. For a 5 A (IB)  
meter, 0.4% of IB is equivalent to 20 mA.  
Frequency Outputs  
Figure 2 shows a timing diagram for the various frequency  
outputs. The high frequency CF output is intended to be used  
for communications and calibration purposes. CF produces a  
90 ms wide, active high pulse (t4) at a frequency that is propor-  
tional to active power. The CF output frequencies are given in  
Table 7. As in the case of F1 and F2, if the period of CF (t5) falls  
below 180 ms, the CF pulse width is set to half the period. For  
example, if the CF frequency is 20 Hz, the CF pulse width is  
25 ms.  
Note that the no-load threshold is not enabled when using the  
high CF frequency mode: SCF = 0, S1 = S0 = 1.  
NEGATIVE POWER INFORMATION  
The ADE7761 detects when the current and voltage channels  
have a phase shift greater than 90°. This mechanism can detect  
wrong connection of the meter or generation of negative power.  
The REVP pin output goes active high when negative power is  
detected, and active low when positive power is detected. The  
REVP pin output changes state as a pulse is issued on CF.  
Rev. A | Page 24 of 28  
 
 复制成功!