欢迎访问ic37.com |
会员登录 免费注册
发布采购

ADE7761ARS-REF 参数 Datasheet PDF下载

ADE7761ARS-REF图片预览
型号: ADE7761ARS-REF
PDF下载: 下载PDF文件 查看货源
内容描述: 电能计量IC ,带有片上故障和中性丢失检测 [Energy Metering IC with On-Chip Fault and Missing Neutral Detection]
分类和应用: 模拟IC信号电路光电二极管
文件页数/大小: 28 页 / 321 K
品牌: ADI [ ADI ]
 浏览型号ADE7761ARS-REF的Datasheet PDF文件第16页浏览型号ADE7761ARS-REF的Datasheet PDF文件第17页浏览型号ADE7761ARS-REF的Datasheet PDF文件第18页浏览型号ADE7761ARS-REF的Datasheet PDF文件第19页浏览型号ADE7761ARS-REF的Datasheet PDF文件第21页浏览型号ADE7761ARS-REF的Datasheet PDF文件第22页浏览型号ADE7761ARS-REF的Datasheet PDF文件第23页浏览型号ADE7761ARS-REF的Datasheet PDF文件第24页  
ADE7761  
Fault with Active Input Greater than Inactive Input  
Calibration Concerns  
If V1A is the active current input (that is, being used for billing),  
and the voltage signal on V1B (inactive input) falls below 93.75%  
of V1A, the fault indicator becomes active. Both analog inputs are  
filtered and averaged to prevent false triggering of this logic  
output. As a consequence of the filtering, there is a time delay of  
approximately 3 s on the logic output FAULT after the fault  
event. The FAULT logic output is independent of any activity on  
outputs F1 or F2. Figure 26 shows one condition under which  
FAULT becomes active. Because V1A is the active input and it is  
still greater than V1B, billing is maintained on V1A, that is, no  
swap to the V1B input occurs. V1A remains the active input.  
Typically, when a meter is being calibrated, the voltage and  
current circuits are separated as shown in Figure 28. This means  
that current passes through only the phase or neutral circuit.  
Figure 28 shows current being passed through the phase circuit.  
This is the preferred option, because the ADE7761 starts billing  
on the input V1A on power-up. The phase circuit CT is con-  
nected to V1A in the diagram. Since there is no current in the  
neutral circuit, the FAULT indicator comes on under these  
conditions. However, this does not affect the accuracy of the  
calibration and can be used as a means to test the functionality  
of the fault detection.  
FAULT  
FILTER  
AND  
V
R
F
1A  
V
V
1A  
1A  
IB  
CT  
COMPARE  
V
A
B
1B  
V
V
RB  
RB  
TO  
C
C
1A  
1B  
V
F
F
1A  
MULTIPLIER  
0V  
AGND  
V
V
1N  
1B  
V
V
1N  
AGND  
IB  
0V  
TEST  
CURRENT  
V
< 93.75% OF V  
1A  
1B  
CT  
FAULT  
R
F
1B  
RA*  
RB*  
VR*  
C
F
<0  
>0  
ACTIVE POINT – INACTIVE INPUT  
V
V
2P  
6.25% OF ACTIVE INPUT  
R
F
2N  
V
Figure 26. Fault Conditions for Active Input Greater than Inactive Input  
C
T
240V RMS  
*RB + VR = RF  
Fault with Inactive Input Greater than Active Input  
Figure 28. Fault Conditions for Inactive Input Greater than Active Input  
Figure 27 illustrates another fault condition. If the difference  
between V1B, the inactive input, and V1A, the active input (that is,  
being used for billing), becomes greater than 6.25% of V1B, the  
FAULT indicator goes active, and there is also a swap over to the  
V1B input. The analog input V1B becomes the active input. Again,  
there is a time constant of about 3 s associated with this swap.  
If the neutral circuit is chosen for the current circuit in the  
arrangement shown in Figure 28, this may have implications for  
the calibration accuracy. The ADE7761 powers up with the V1A  
input active as normal. However, because there is no current in  
the phase circuit, the signal on V1A is zero. This causes a fault to  
be flagged and the active input to be swapped to V1B (neutral).  
The meter can be calibrated in this mode, but the phase and  
neutral CTs might differ slightly. Because under no-fault condi-  
tions all billing is carried out using the phase CT, the meter  
should be calibrated using the phase circuit. Of course, both  
phase and neutral circuits can be calibrated.  
V1A does not swap back to being the active channel until V1A is  
greater than V1B and the difference between V1A and V1B—in this  
order—becomes greater than 6.25% of V1A. However, the  
FAULT indicator becomes inactive as soon as V1A is within  
6.25% of V1B. This threshold eliminates potential chatter  
between V1A and V1B.  
FAULT  
FILTER  
AND  
COMPARE  
V
V
1A  
1A  
MISSING NEUTRAL MODE  
V
A
B
1B  
The ADE7761 integrates a novel fault detection that warns and  
allows the ADE7761 to continue to bill in case a meter is  
connected to only one wire (see Figure 29). For correct  
operation of the ADE7761 in this mode, the VDD pin of the  
ADE7761 must be maintained within the specified range (5 V  
5%). The missing neutral detection algorithm is designed to  
work over a line frequency of 45 Hz to 55 Hz.  
V
V
TO  
1A  
1B  
MULTIPLIER  
0V  
V
V
1N  
1B  
AGND  
V
< 93.75% OF V  
1B  
1A  
FAULT + SWAP  
<0  
>0  
ACTIVE POINT – INACTIVE INPUT  
6.25% OF INACTIVE INPUT  
Figure 27. Fault Conditions for Inactive Input Greater than Active Input  
Rev. A | Page 20 of 28  
 
 
 
 复制成功!