欢迎访问ic37.com |
会员登录 免费注册
发布采购

ADE7761AARS-REF 参数 Datasheet PDF下载

ADE7761AARS-REF图片预览
型号: ADE7761AARS-REF
PDF下载: 下载PDF文件 查看货源
内容描述: 电能计量IC ,带有片上故障和中性丢失检测 [Energy Metering IC with On-Chip Fault and Missing Neutral Detection]
分类和应用:
文件页数/大小: 24 页 / 527 K
品牌: ADI [ ADI ]
 浏览型号ADE7761AARS-REF的Datasheet PDF文件第14页浏览型号ADE7761AARS-REF的Datasheet PDF文件第15页浏览型号ADE7761AARS-REF的Datasheet PDF文件第16页浏览型号ADE7761AARS-REF的Datasheet PDF文件第17页浏览型号ADE7761AARS-REF的Datasheet PDF文件第19页浏览型号ADE7761AARS-REF的Datasheet PDF文件第20页浏览型号ADE7761AARS-REF的Datasheet PDF文件第21页浏览型号ADE7761AARS-REF的Datasheet PDF文件第22页  
ADE7761A  
Fault with Active Input Greater than Inactive Input  
Calibration Concerns  
If V1A is the active current input (that is, being used for billing),  
and the voltage signal on V1B (inactive input) falls below 93.75%  
of V1A, the fault indicator becomes active. Both analog inputs  
are filtered and averaged to prevent false triggering of this logic  
output. As a consequence of the filtering, there is a time delay of  
approximately 3 sec on the logic output FAULT after the fault  
event. The FAULT logic output is independent of any activity on  
outputs F1 or F2. Figure 28 shows one condition under which  
FAULT becomes active. Because V1A is the active input and it is  
still greater than V1B, billing is maintained on V1A, that is, no  
swap to the V1B input occurs. V1A remains the active input.  
Typically, when a meter is being calibrated, the voltage and  
current circuits are separated, as shown in Figure 30. This  
means that current passes through only the phase or neutral  
circuit. Figure 30 shows current being passed through the phase  
circuit. This is the preferred option because the ADE7761A  
starts billing on the input V1A on power-up. The phase circuit  
CT is connected to V1A in Figure 30. Because there is no current  
in the neutral circuit, the FAULT indicator comes on under  
these conditions. However, this does not affect the accuracy of  
the calibration and can be used as a means to test the functionality  
of the fault detection.  
FAULT  
FILTER  
AND  
V
R
1A  
F
V
V
1A  
1A  
IB  
CT  
V
COMPARE  
A
B
1B  
V
V
TO  
RB  
RB  
1A  
C
C
V
F
F
1A  
MULTIPLIER  
0V  
AGND  
V
V
1N  
V
V
AGND  
< 93.75% OF V  
1N  
1B  
IB  
0V  
TEST  
V
1B  
1A  
1B  
CURRENT  
CT  
FAULT  
<0  
R
F
1B  
1
RA  
C
F
1
1
RB  
>0  
ACTIVE POINT – INACTIVE INPUT  
V
V
2P  
VR  
6.25% OF ACTIVE INPUT  
R
F
2N  
Figure 28. Fault Conditions for Active Input Greater than Inactive Input  
V
C
T
240V rms  
Fault with Inactive Input Greater than Active Input  
1
RB + VR = RF.  
Figure 29 illustrates another fault condition. If the difference  
between V1B, the inactive input, and V1A, the active input (that  
is, being used for billing), becomes greater than 6.25% of V1B,  
the FAULT indicator becomes active and a swap over to the V1B  
input occurs. The analog input V1B becomes the active input.  
Again, a time constant of about 3 sec is associated with this  
swap. V1A does not swap back to the active channel until V1A is  
greater than V1B and the difference between V1A and V1B—in  
this order—becomes greater than 6.25% of V1A. However, the  
FAULT indicator becomes inactive as soon as V1A is within  
6.25% of V1B. This threshold eliminates potential chatter  
between V1A and V1B.  
Figure 30. Conditions for Calibration of Channel B  
If the neutral circuit is chosen for the current circuit in the  
arrangement shown in Figure 30, this may have implications for  
the calibration accuracy. The ADE7761A powers up with the  
V1A input active as normal. However, because there is no  
current in the phase circuit, the signal on V1A is zero. This  
causes a fault to be flagged and the active input to be swapped  
to V1B (neutral). The meter can be calibrated in this mode, but  
the phase and neutral CTs may differ slightly. Because under  
no-fault conditions all billing is carried out using the phase CT,  
the meter should be calibrated using the phase circuit. Of  
course, both phase and neutral circuits can be calibrated.  
FAULT  
FILTER  
AND  
COMPARE  
V
V
1A  
1A  
A
V
MISSING NEUTRAL MODE  
1B  
V
V
TO  
1A  
The ADE7761A integrates a novel fault detection that warns  
and allows the ADE7761A to continue to bill in case a meter is  
connected to only one wire (see Figure 31). For correct  
operation of the ADE7761A in this mode, the VDD pin of the  
ADE7761A must be maintained within the specified range (5 V  
5%). The missing neutral detection algorithm is designed to  
work over a line frequency of 45 Hz to 55 Hz.  
MULTIPLIER  
0V  
V
V
1N  
AGND  
< 93.75% OF V  
B
1B  
V
1A  
1B  
1B  
FAULT + SWAP  
<0  
>0  
ACTIVE POINT – INACTIVE INPUT  
6.25% OF INACTIVE INPUT  
Figure 29. Fault Conditions for Inactive Input Greater than Active Input  
Rev. 0 | Page 18 of 24