Industrial Power Supplies
TBL Series
15 to 150 Watt
Input Specifications
Input voltage
– AC nominal rated
100 – 240 VAC; 50/60 Hz
TBL 150 models: 100 – 120 / 220 – 240 VAC; 50/60 Hz
85 – 264 VAC; 47 – 63 Hz
– AC range (designed for)
TBL 150 models: 85 – 132 / 187 – 264 VAC; 47 – 63 Hz
120 – 373 VDC (except TLB 150 models)
5% below 90 VAC or 127 VDC
– DC range (designed for)
– Power derating at low input voltage
Harmonic limits
EN 61000-3-2, Class A
6.0 A
Recommended circuit breaker (characteristic C or slow blow fuse)
Output Specifications
Output voltage adjustable range
5 VDC model: 5.0 – 5.2 VDC
12 VDC models: 12 – 16 VDC
24 VDC models: 24 – 28 VDC
Output regulation
1 %
Ripple and noise (20MHz bandwidth)
Electronic short circuit protection
<100 mV pk-pk
current limitation at 100 – 150 % typ.
(automatic recovery)
Overvoltage protection, trigger point
5 VDC model: 5.5 – 7.5 VDC
12 VDC models: 16 – 24 VDC
TBL 030-124, TBL 150-124: 30 – 37 VDC
TBL 015-124, TBL 060-124, TBL 090-124: 29 – 44 VDC
Hold-up time
115 VAC
min. 10 ms
230 VAC
min. 20 ms
General Specifications
Temperature ranges
– Operating
– Storage
–25°C to +70°C max.
–40°C to +85°C max.
2.5 %/K above 60°C
5 – 95 % rel. H
Power derating
Humidity (non condensing)
Temperature coefficient
0.02 %/K
Reliability, calculated MTBF at +25°C acc. to IEC 61709
TBL 015: >1,500 Mio h
TBL 060: >2,100 Mio h
all other models: >1,300 Mio h
Safety standards
UL 508
UL 1310, class II
15 – 90 W models:
IEC/EN 60950-1, UL 60950-1, EN 50178,
EN 60204, EN 61558-2-8
CSA C22.2 No. 60950-1 2003
Safety approvals
– CB report (IEC/EN 60950-1)
– UL approval
www.tracopower.com/products/tbl-cb.pdf
UL 508 listed
www.tracopower.com/products/tbl-ul508.pdf
15 – 90 W models: UL 1310 listed
www.tracopower.com/products/tbl-ul1310.pdf
www.tracopower.com/products/tbl-csa.pdf
www.tracopower.com/products/tbl-siq.pdf
www.tracopower.com/products/tbl-bv.pdf
– CSA certification (UL 60950-1, CSA 60950-1-03)
– SIQ certificate (IEC/EN 60950-1)
– Bureau Veritas
Electromagnetic compatibility (EMC), emissions
– Conducted RI suppression on input
– Radiated RI suppression
EN 61000-6-3
EN 55022 class B
EN 55022 class B
Electromagnetic compatibility (EMC), immunity
EN 61000-6-2
– Electrostatic discharge (ESD)
– Radiated RF field immunity
– Electrical fast transient / burst immunity
– Surge immunity line – ground
– Surge immunity line – line
– Surge immunity output
– Immunity to conducted RF disturbances
– Mains voltage dips and interruptions
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-5
EN 61000-4-5
EN 61000-4-6
4 kV / 8 kV
3 V/m
1 kV / 0.5 kV
2 kV
1 kV
0.5 kV
3 V
EN 61000-4-11 30 % /10 mS, 60 % /100 mS
http://www.tracopower.com