Input 36-75 V, Output up to 39 A / 468 W
circuit on the input source, this fuse will provide the
following functions:
Safety Specification
General information
Isolate the fault from the input power source so as not
to affect the operation of other parts of the system
Protect the distribution wiring from excessive current
and power loss thus preventing hazardous overheating
Ericsson Power Modules DC/DC converters and DC/DC
regulators are designed in accordance with the safety
standards IEC 60950-1, EN 60950-1 and UL 60950-1
Safety of Information Technology Equipment.
The DC/DC converter output is considered as safety extra
low voltage (SELV) if one of the following conditions is met:
IEC/EN/UL 60950-1 contains requirements to prevent injury
or damage due to the following hazards:
The input source has double or reinforced insulation
from the AC mains according to IEC/EN/UL 60950-1
The input source has basic or supplementary insulation
from the AC mains and the input of the DC/DC
converter is maximum 60 Vdc and connected to
protective earth according to IEC/EN/UL 60950-1
The input source has basic or supplementary insulation
from the AC mains and the DC/DC converter output is
connected to protective earth according to
Electrical shock
Energy hazards
Fire
Mechanical and heat hazards
Radiation hazards
Chemical hazards
On-board DC/DC converters and DC/DC regulators are
defined as component power supplies. As components
they cannot fully comply with the provisions of any safety
requirements without “conditions of acceptability”.
Clearance between conductors and between conductive
parts of the component power supply and conductors on
the board in the final product must meet the applicable
safety requirements. Certain conditions of acceptability
apply for component power supplies with limited stand-off
(see Mechanical Information for further information). It is
the responsibility of the installer to ensure that the final
product housing these components complies with the
requirements of all applicable safety standards and
regulations for the final product.
IEC/EN/UL 60950-1
Non - isolated DC/DC regulators
The DC/DC regulator output is SELV if the input source
meets the requirements for SELV circuits according to
IEC/EN/UL 60950-1.
Component power supplies for general use should comply
with the requirements in IEC/EN/UL 60950-1 Safety of
Information Technology Equipment. Product related
standards, e.g. IEEE 802.3af Power over Ethernet, and
ETS-300132-2 Power interface at the input to telecom
equipment, operated by direct current (dc) are based on
IEC/EN/UL 60950-1 with regards to safety.
Ericsson Power Modules DC/DC converters and DC/DC
regulators are UL 60950-1 recognized and certified in
accordance with EN 60950-1. The flammability rating for all
construction parts of the products meet requirements for
V-0 class material according to IEC 60695-11-10, Fire
hazard testing, test flames – 50 W horizontal and vertical
flame test methods.
Isolated DC/DC converters
Galvanic isolation between input and output is verified in an
electric strength test and the isolation voltage (Viso) meets
the voltage strength requirement for basic insulation
according to IEC/EN/UL 60950-1.
It is recommended to use a slow blow fuse at the input of
each DC/DC converter. If an input filter is used in the circuit
the fuse should be placed in front of the input filter. In the
rare event of a component problem that imposes a short