G4 Digital AC Output Modules
Specifications
G4OAC5
G4OAC5FM*
G4OAC5A
G4OAC5AFM*
G4OAC5A5
G4OAC5A5FM*
Units
G4OAC5MA
G4OAC5AMA
Nominal line voltage
Output voltage range
VAC
VAC
120
120/240
24–280
120/240
24–280
120
120/240
24–280
12–140
12–140
Diagnostic
switch
Diagnostic
switch
Key feature
—
—
—
Normally closed
Current rating:
At 45 °C ambient
At 70 °C ambient
A
A
3
2
3
2
3
2
3
2
3
2
UL Motor Load Rating
A
1.5
1.5
1.5
1.5
1.5
Isolation input-to-
output (transient):
1 ms
volts
4000
1500
4000
1500
4000
1500
4000
1500
4000
1500
1 minute
Off-state leakage at
nominal voltage (60 Hz)
mARMS
5
1.25/2.5
1.25/2.5
5
1.25/2.5
Nominal logic voltage
Logic voltage range
Logic pickup voltage
Logic dropout voltage
VDC
VDC
VDC
VDC
5
4–8
4
5
4–8
4
5
4–8
4
5
4–8
4
5
4–8
4
1
1
1
1
1
Logic input current at
nominal logic voltage
mA
12
12
12
12
12
Control resistance
(Rc in schematic)
ohms
220
220
220
220
220
One-cycle surge
A peak
milliseconds
milliseconds
VAC
80
≤8.3**
≤8.3***
500
80
≤8.3**
≤8.3***
500
80
≤8.3**
≤8.3***
500
80
≤8.3**
≤8.3***
500
80
≤8.3**
≤8.3***
500
Turn-on time @ 60 Hz
Turn-off time @ 60 Hz
Peak repetitive voltage
Minimum load current
mA
20
20
20
20
20
Output voltage drop
maximum peak
V
1.6
25–65
200
1.6
25–65
200
1.6
25–65
200
1.6
25–65
200
1.6
25–65
200
Operating frequency
dV/dT-off-state
Hz
V/micro-
seconds
snubbed for
0.5 power
factor load
snubbed for
0.5 power
factor load
snubbed for
0.5 power
factor load
snubbed for
0.5 power
factor load
snubbed for
0.5 power
factor load
dV/dT-commutating
--
Temperature
Operating:
Storage:
°C
°C
-30 to +70
-30 to +85
-30 to +70
-30 to +85
-30 to +70
-30 to +85
-30 to +70
-30 to +85
-30 to +70
-30 to +85
* Part numbers ending in FM are Factory Mutual approved.
** One-half cycle maximum. Module turns on at the zero volt crossing of the AC sine wave.
*** One-half cycle maximum. Module turns off at the zero current crossing of the AC sine wave.
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2012 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
PAGE
2