wires  
torques  
screwdriver  
Connections .  
L
L
(mm2)  
Ø
For the output terminals, the wire cross sections must  
screwdriver  
be adapted to the load current and to the overcurrent protection  
device characteristics. The relay rated voltage must be adapted  
to the mains rated voltage.  
control  
1 x(0,75-->2,5)  
L = 6mm  
0,4N.m  
(0,6N.m max)  
3,5x0,5mm  
Ø
celpac use screw clamp connections.  
Power  
1x(1,5-->16) 1 x(1,5-->10)  
L = 10mm  
1,2N.m  
(1,8N.m max)  
Pozidriv2/  
0,8x5,5 (1x6)  
Mounting  
Ø
Warning : only in vertical position. The user should protect heat sensitive materials as  
well as persons against any contacts with the heatsink. For non vertical mounting , the load  
current must be 50% lower than the rated one . For a good cooling, the SSR needs an air  
convection. Less convection air produces an abnormal heating. Keep a distance between  
the upper SSR and the lower SSR. In case of no space between two SSR ( zero space  
between two SSRs) , please reduce the load current. For further details refer to below :  
Ø Derating current with no space between SSRs  
AC-51 nominal currents are given with a space of 22,5mm between each SSR, for a  
permanent current during a minimum time of 8 hours in air calm according to IEC60947-4-3.  
In case of non permanent currents or in case of SSRs are mounted with no space, you must  
check the heatsink temperature never exceed 90°C. When the SSRs are mounted side to  
side ( no space between each relay) a derating current of 25% must be take into account.  
A forced cooling ( fan inside the cabinet) improves significantly the thermal performances.  
vert ical  
posit ion  
8 0 mm  
Typical application : LOADS  
SIL product is designed mainly for AC-51 résistive load. AC-53 motor current are  
also given . For other loads, check the inrush current at turn ON and possible overvoltages  
at turn OFF or consult us :  
* AC-55b : Incandescent lamps : Inrush current is generally 10 times In during few 10ms.  
So limit the nominal current at about 15A.  
* AC-55a : Electric discharge lamp : These loads often have overcurrent at turn ON and  
overvoltage at turn OFF, so we advise to use 400VAC SSR on 230VAC mains.  
* AC-56a : Transformers loads : Very high inrush current up to 100 times In . We advise to  
use random SSR.  
1 ~  
* AC-56b : Capacitors loads : Very high current at turn ON and overvolatge at turn OFF,  
please consult us with 1600V peak SSR with high inrush current.  
Fuse  
Fusible  
Protection :  
2
2
To protect the SSR against a short-circuit of the load , use a fuse with a I t value = 1/2 I t  
value specified page 2. A test has been made with FERRAZ fuse ( see page 2).  
L1  
T1  
It is possible to protect SSR by MCB ( miniature circuit breaker). In this case, see application  
2
2
note ( SSR protection) and use a SSR with high I t value (5000A s minimum).  
EMC :  
Ø
Immunity :  
We give in our data-sheets, the immunity level of our SSRs according to the main  
standards for this type of products : EN61000-4-4 &5. You can see the high immunity level  
in comparison with the products on the market.  
A1  
A2  
Ø
Emission:  
cont rol  
SSRs are complex devices which must be interconnected with other equipment  
Load  
Charge  
(loads, cables,etc.) to form a system. Because the other equipment or the interconnections  
may not be under the control of celduc it shall be the responsibility of the system integrator  
to ensure that systems containing SSRs comply with the requirements of any rules and  
regulations applicable at the system level. The very low zero cross voltage (<20V) improves  
the conducted emission level in comparison with most of SSR on the market with zero cross  
voltage higher than 50V. Consult celduc laboratory which can make some tests in your  
application.  