 浏览型号2032-X0043HX-25D的Datasheet PDF文件第1页浏览型号2032-X0043HX-25D的Datasheet PDF文件第2页浏览型号2032-X0043HX-25D的Datasheet PDF文件第3页浏览型号2032-X0043HX-25D的Datasheet PDF文件第4页浏览型号2032-X0043HX-25D的Datasheet PDF文件第5页浏览型号2032-X0043HX-25D的Datasheet PDF文件第6页浏览型号2032-X0043HX-25D的Datasheet PDF文件第7页浏览型号2032-X0043HX-25D的Datasheet PDF文件第8页  
Safety Isolation System  
ElectroGuard  
Wire Length Considerations/Ordering Instructions  
The total wire length for the 5 RLS to be wired to the Control  
Module will be: 100ft + 400ft + 200ft + 600ft + 1,000ft = 2,300ft  
b. Sum the full-load currents of all the motor loads to be  
connected to the Safety Isolation System. To this value add  
the current values of all resistive loads to be connected to  
the Safety Isolation System. This value is the “combined  
load full-load current.”  
c. Find the horsepower or kilowatt rating of a single motor with  
a full-load current value greater than or equal to the  
“combined load full-load current” value determined in Step  
“b”.  
Per the table entitled Total Wire Length for Remote Lockout Stations on  
page 12-18, the maximum allowable wire length for 14AWG wire is  
4,600ft for the RLS to be wired to the Control Module. This portion  
of the installation will be within the maximum wire length permitted.  
Next, we need to check the wire length calculation for the RLS to be  
wired to the Expansion Module.  
For RLS # 6: wire length = 1000ft x 2 = 200ft  
For RLS # 7: wire length = 850ft x 2 = 1700ft  
For RLS # 8: wire length = 750ft x 2 = 1500ft  
d. Select the Safety Isolation System that meets or exceeds this  
horsepower or kilowatt rating at the required voltage and  
frequency.  
e. Sum the locked-rotor currents of all the motor loads to be  
connected to the Safety Isolation System. To this value add  
the current values of all resistive loads to be connected to  
the Safety Isolation System. This value is the “combined  
load locked-rotor current”.  
f. Find the horsepower or kilowatt rating of a single motor with  
a locked-rotor current value greater than or equal to the  
“combined load locked-rotor current” value determined in  
Step “e”.  
The total wire length for the 3 RLS to be wired to the Expansion  
Module will be: 2000ft + 1700ft + 1500ft = 5,200ft  
Per the table entitled Total Wire Length for Expansion Modules on page  
12-18, the maximum allowable wire length for 14AWG wire is  
40,000ft for the RLS to be wired to the Expansion Module. This  
portion of the installation will also be within the maximum wire  
length permitted.  
Ordering Instructions  
g. Select the Safety Isolation System that meets or exceeds this  
horsepower or kilowatt rating at the required voltage and  
frequency.  
1. Determine the Catalogue Number of the Safety Isolation System  
based on the rating of the load(s) to which it will be connected as  
follows:  
h. Compare the ratings of the Safety Isolation Systems selected  
in Steps “d” and “g”. Select the larger of the two systems for  
your application.  
If the Safety Isolation System is connected to a single motor load,  
the horsepower or kilowatt rating of the system should be  
determined as follows:  
a. Select the Safety Isolation System that meets or exceeds the  
horsepower or kilowatt rating of the load at the required  
voltage and frequency.  
2. Determine how many Remote Lockout Stations are required for  
the application.  
3. Determine how many Expansion Modules (if any) are required  
for the application.  
4. Pick suitable enclosure type(s) for the Safety Isolation System  
Power Panel, Remote Lockout Stations and enclosed modules  
(e.g., Expansion Modules, Pneumatic Isolation Module).  
5. Determine what, if any, factory installed options are required for  
the application (e.g. Pneumatic Isolation, Status Communication  
to remote PLC, metering).  
If the Safety Isolation System is connected to two or more  
motors or one or more motors in combination with other loads,  
the horsepower or kilowatt rating of the system should be  
determined as follows:  
a. Identify the types of loads (i.e. motor, resistive) and the values  
of the currents of each of the loads (i.e. steady-state current  
for resistive loads, full-load and locked-rotor currents for  
motor loads) to be connected to the Safety Isolation System.  
12-19