Single Output Enclosed Switchers
15-600 Watts
CPP Series
•
T
HE
XP
ERTS
I
N
P
OWER
85-264 VAC Universal Input
•
Single Outputs
•
High Reliability
•
Power Factor Corrected
•
Remote Control Available
•
Parallel Operation Available
•
Din Rail Mounting Accessories Available
Specification
Input
Input Voltage
Power Factor
Input Frequency
Inrush Current
•
•
•
•
85-264 VAC
0.95 typical (230 V) up to 0.99 at 100 V
(CPP50 & above only) at full load
47-63 Hz
40 A max
General
LED Indicator
Parallel Operation
•
•
Indicates output on
Master/Slave operation available -
300 & 600 watt models -
Contact Sales for details
Ranges 65% (3 V) to 80% (24 V) output
0.75 mA max at 60 Hz
See DIN, Wall & Panel Mounting
Accessories
Output
Hold Up Time
Output Voltage
Remote Control
Voltage Adjustment
Line Regulation
Load Regulation
Ripple & Noise
Overload Protection
•
•
•
•
•
•
•
•
20 ms typical at low line & full load
(100 ms typical at 230 V)
See Table
Standard on 300 & 600 watt models
Optional on all others add suffix ‘-R’
±10%trim min
(-5% to +20% 3 V models)
0.4% max over input range
0.8% max for 100% load change
40 mV pk-pk typical (150 mV max)
Operates at >105% of rating &
recovers automatically
(300 & 600 W constant current)
115-140%
(except 3 V units : 4.00-5.25 V )
0.02%/°C
Efficiency
Leakage Current
Mounting Options
•
•
•
Environmental
Operating
•
Temperature
Storage Temperature •
Relative Humidity
•
Vibration
•
-10 °C to +65 °C,
derate above 50 °C - Contact Office
-20 °C to +75 °C
20-90% RH
20 G, 11 ms once each X, Y & Z axis
EMC & Safety
Safety Approvals
Immunity
EMC
•
•
•
EN60950, UL1950, CSA22.2 No. 234,
VDE 0160
IEC 1000-3-2
CISPR22 Level B, FCC Level B
Overvoltage
Protection
Temperature
Coefficient
•
•
•
•
www.xpplc.com
sales@xpplc.com