AC-DC Power Supplies
ALM150 Series
General
Characteristic
Minimum
Typical
Maximum
Units
%
Notes & Conditions
See curves.
Efficiency
93
4000
1500
VAC
VAC
VAC
2 x MOPP
Isolation: Input to Output
Input to Ground
1 x MOPP (Class I versions only)
Output to Ground
500
140
190
Class I versions only
PFC
Main Converter
45
85
Switching Frequency
kHz
3
Power Density
4.83
>300
W/in
Mean Time Between Failure
Weight
kHrs
lb (g)
MIL-HDBK-217F at 25 °C GB
1.4 (635)
Efficiency Curves
ALM150PS12
100.00%
90.00%
80.00%
70.00%
60.00%
115 V
230 V
10%
20%
30%
40%
50%
60%
70%
80%
90% 100%
Load
ALM150PS24
100.00%
90.00%
80.00%
70.00%
60.00%
115 V
230 V
10%
20%
30%
40%
50%
60%
70%
80%
90% 100%
Load
EMC: Emissions
Phenomenon
Standard
Test Level
Notes & Conditions
Emissions
Harmonic Current
Voltage Flicker
EN55032
EN61000-3-2
EN61000-3-3
Level B
Class A
Conducted & Radiated
www.xppower.com
3