Environmental
Characteristic
Minimum
Typical
Maximum
Units
ºC
Notes & Conditions
Derate linearly to 60% load at 60 ºC from
+40 °C. (See fig.10)
Operating Temperature
0
+60
71
60
ºC
100% Load, with TAMB +40 ºC
Case Temperature
(IEC60601 3rd Edition)
70% Load Maximum, with TAMB +40 ºC
10% Load Maximum, with TAMB +40 ºC
48
Storage Temperature
Cooling
-40
5
+85
ºC
Convection cooled, see fig.10
Non-condensing
Humidity
95
%RH
m
Operating Altitude
Ingress Protection
3000
IP22
3 x 30 g/11 ms shocks in both +ve & -ve
directions along the 3 orthogonal axis,
total 18 shocks.
Shock
Vibration
Three axis 5-500 Hz at 2 g x 10 sweeps
Derating Curve
Figure 10
100%
60%
0
10
20
Ambient Temperature (ºC)
40
60
Electromagnetic Compatibility - Immunity
Phenomenon
Low Voltage PSU EMC
Harmonic Current
ESD
Standard
Test Level
Criteria
Notes & Conditions
EN61204-3
High severity level
as below
EN61000-3-2
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
Class A
3
A
A
A
A
A
A
A
B
A
B
A
A
A
B
Radiated
3
EFT
3
Surges
Installation class 3
Conducted
Magnetic Field
3
3
Dip: 30% 500 ms
Dip: 60% 200 ms
EN61000-4-11
EN60601-1-2
Dip: 80% 5000 ms
Dip: 100% 5000 ms
Dip: 30% 25 AC Cycles
Dip: 60% 5 AC Cycles
Dip: 100% 0.5 AC Cycles
Dips and Interruptions
230 VAC 100% load, 100 VAC 80% load
230 VAC 100% load, 100 VAC 15% load
Int.:
>95% 5000 ms