BCM4414xG0F4440yzz
Electrical Specifications (Cont.)
Specifications apply over all line and load conditions, unless otherwise noted; boldface specifications apply over the temperature range of
–40°C ≤ TCASE ≤ 100°C (T-Grade); all other specifications are at TCASE = 25ºC unless otherwise noted.
Attribute
Symbol
Conditions / Notes
Min
Typ
Max
Unit
Powertrain Supervisory Limits Specification – Forward Direction Operation (High Voltage Side to Low Voltage Side)
• These supervisory limits are set in the internal controller and can be reconfigured or disabled through PMBus™.
• When disabled, the powertrain protections presented in the previous table will intervene during fault events.
HI Side Overvoltage
Lockout Threshold
VHI_OVLO+
VHI_OVLO–
VHI_OVLO_HYST
tHI_OVLO
730
700
750
730
20
780
740
V
V
HI Side Overvoltage
Recovery Threshold
HI Side Overvoltage
Lockout Hysteresis
V
HI Side Overvoltage
Lockout Response Time
100
360
380
20
µs
V
HI Side Undervoltage
Lockout Threshold
VHI_UVLO–
350
370
370
399
HI Side Undervoltage
Recovery Threshold
VHI_UVLO+
VHI_UVLO_HYST
tHI_UVLO
V
HI Side Undervoltage
Lockout Hysteresis
V
HI Side Undervoltage
Lockout Response Time
100
50
µs
ms
A
From VHI_DC = VHI_UVLO+ to powertrain active (i.e., one
time start up delay from application of VHI_DC to VLO_DC
HI Side Undervoltage Start Up Delay tHI_UVLO+_DELAY
)
LO Side Overcurrent
ILO_OUT_OCP
42
50
70
Trip Threshold
LO Side Overcurrent
tLO_OUT_OCP
Effective internal RC filter
Internal
2
ms
°C
°C
Response Time Constant
Overtemperature
tOTP+
125
Shutdown Threshold
Overtemperature
tOTP–
Internal
105
110
115
Recovery Threshold
C-Grade
T-Grade
–25
–45
Undertemperature
tUTP
°C
s
Shutdown Threshold (Internal)
Start up into a persistent fault condition. Non-latching
fault detection given VHI_DC > VHI_UVLO+
Undertemperature Restart Time
tUTP_RESTART
3
BCM® in a VIA™ Package
Page 8 of 43
Rev 1.2